46 CLCH-SVX03C-EN
Component Installation Requirements
Traq Damper Connections
Size the duct connections to attach to the specified portion on the face of the Traq damper module.
For a mitered corner, provide one hydraulic duct diameter between the entering face of the Traq
dampers and the duct turn. For a radius elbow, or sweep, place the elbow directly against the face
of the Traq dampers (see Figure 42).
External Face-and-Bypass Connections
The external face-and-bypass damper modules will require a field fabricated duct to direct the
bypass air into the appropriate module. Duct sizing recommendations are listed in Table 13.
Figure 42. Traq damper duct connections
Traq damper
mixing box
Inlet duct
Traq damper
mixing box
Radius elbow
(sweep)
Mitered
corner
W
d
H
d = 1 hydraulic duct diameter = 2 x W x H
W + H
Table 13. Recommended bypass duct sizes (inches)
Unit size Duct height Duct width
31227
6 14 40
81444
10 14 56
12 18 60
14 18 64
17 18 70
21 24 72
25 24 74
30 24 87
35 28 91
40 28 104
50 28 115
57 40 115
66 40 132
80 40 132
100 40 147
120 40 174