CLCH-SVX03C-EN 79
Startup
Fan Inlet Airflow Measuring System
Figure 72. Piezometer ring airflow
measurement
Table 19. M-Series fan inlet dimensions
Unit Size Inside Diameter (in.) Unit Size Inside Diameter (in.)
03A 7.810 30A 21.259
03B 7.810 30B 18.250
D03 6.100 D30 17.080
E03 6.100 E30 17.080
03P 8.75 F30 15.160
06A 10.250 G30 15.160
06B 9.066 30P 22.90
D06 8.540 35A 24.000
E06 8.540 35B 21.259
06P 9.64 D35 17.080
08A 11.500 E35 17.080
08B 10.250 F35 15.160
D08 8.540 G35 15.160
E08 8.540 35P 22.90
08P 10.86 40A 26.037
10A 12.875 40B 24.000
10B 11.500 D40 19.290
D10 10.820 E40 19.290
A fan inlet airflow measuring system
with a piezometer ring is available on
many centrifugal and plenum fans.
Each system comes with a differential
pressure transmitter. The piezometer
ring is connected to the LO port of the
transmitter and the reference
pressure point is connected to (or
actually is) the HI port of the
transmitter.
E10 10.820 F40 17.080
F10 8.540 G40 17.080
G10 8.540 40P 25.56
10P 11.93 50A 28.404
12A 12.124
50B 26.037
12B 12.875 D50 21.650
D12 12.000
E50 21.650
E12 12.000 F50 19.290
F12 10.820
G50 19.290
G12 10.820 50P 28.34
12P 13.06
57A 28.404
14A 15.625 57B 26.037
14B 14.124
D57 21.650
D14 12.000 E57 21.650
E14 12.000
F57 19.290
F14 10.820 G57 19.290
G14 10.820
57P 34.91
14P 14.43 66A 28.404
17A 17.125
B66 29.040
17B 15.625 D66 24.020
D17 13.460
E66 24.020
E17 13.460 F66 21.650
F17 12.000
G66 21.650
G17 12.000 66P 34.91
17P 16.06
A80 29.040
21A 18.250 B80 29.040
21B 17.125
80D 26.890
D21 15.160 80E 26.890
E21 15.160
80F 24.010
F21 13.460 80G 24.010
G21 13.460
80P 39.06
21P 18.37 A100 32.740
25A 21.569
B100 32.740
25B 18.250 100D 30.000
D25 15.160
100E 30.000
E25 15.160 100F 26.890
F25 13.460
100G 26.890
G25 13.460 100P 42.85
25P 20.63
A120 32.740
B120 32.740
120D 33.460
120E 33.460
120F 30.000
120G 30.000
120P 42.85