with splash guard.
Gasket used on sides and
top channels between modules.
Wrap corners. No seams in corners.
HF
HF
HAH
White Butyl tape required between:
-adjacent drain pans
-adjacent splash guard with J channels
-between coil module and module
downstream of a coil
Note: If air gaps are present after
module-to-module bolt up, then compress
the gasket joint with a clamp and install a
center bracket.
Foam drain pan (3-30)
Extra-large drain pan and
all module sizes (35-57)
Airflow
Airflow
Rt side view
Rt side view
Note: Two strips required
Tape must be flush with top edge.
HAH
HAH
HAH
HAH
HAH
HAH
HAH