EasyManua.ls Logo

Trane Climate Changer M Series - Page 51

Trane Climate Changer M Series
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CLCH-SVX03C-EN 51
Coil Piping and Connections
Figure 46. Drain pan trapping for module under negative pressure
Figure 47. Drain pan trapping for module under positive pressure
Normal operation
L
H
J
L = H + J + pipe diameter
where:
H = 1 inch for each inch of negative
pressure* plus 1 inch
J = 1/2 H
*Negative pressure = total unit static
pressure at worst case (loaded filters)
minus external pressure
K
H
L
L = H + K + pipe diameter
where:
K = 1/2 inch (minimum)
H = 1/2 inch plus the total unit
static pressure at worst case
(loaded filters)

Table of Contents

Related product manuals