CG-SVX027D-GB
45
11UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 55 50 42 37 37 31 30 46
FWD 08 2 57 54 47 40 30 38 40 50
3 58 57 50 42 32 40 43 53
1 57 51 45 42 34 33 28 48
FWD 10 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 57 51 45 42 34 33 28 48
FWD 12 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 56 62 50 48 39 38 36 56
FWD 14 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
FWD 20 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 56 55 55 53 46 45 42 57
FWD 08 2 63 62 60 60 53 53 53 64
3 66 65 63 62 56 55 57 67
1 62 58 55 58 51 48 44 61
FWD 10 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 62 58 55 58 51 48 44 61
FWD 12 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 66 65 65 65 57 50 46 68
FWD 14 2 73 72 69 71 64 59 57 74
3 78 76 73 75 69 64 63 78
1 68 72 64 64 56 52 50 69
FWD 20 2 76 76 68 71 65 61 61 75
3 78 79 71 74 69 66 66 78
Operation
Control System
Unit operation is intergrally managed by the
microprocessor-based unit controller.
Unit Operation
Check that the chilled water pump(s) operates correctly
Start up the unit following procedure described in
the unit controller user guide. The unit will operate
correctly when there is sufficient water flow. The
compressors will start up if the evaporator water
leaving temperature is above the control module
setpoint.
Weekly start up
Check that the chilled water pump(s) operates correctly
Start up the unit following procedure described in the
unit controller user guide
Weekend shutdown
If the unit needs to be shut down for a short period of
time, stop the unit following procedure described in
the unit controller user guide. (See «Clock» menu)
If the unit is shut down for a longer period, see under
«Seasonal shutdown», below
Ensure that all safeties are taken to prevent frost
damages during negative ambient temperature
Do not put the general disconnect switches to
off, except if the unit is drained. Trane does not
recommend draining the unit, due to the fact that it
increases corrosion
Seasonal shutdown
Check water flows and interlocks
Check glycol % in the chilled water circuit if glycol
presence is required
Carry out leak test
Carry out oil analysis
Record operating pressures, temperatures, amperages
and voltage
Check operation of machines/ compare conditions of
operation against original commissioning data
Stop the unit following procedure described on the
unit controller user guide
Ensure that all safeties are taken to prevent frost
damages during negative ambient temperature
Fill out the visit log sheet and review with the
operator - Do not put the general disconnect switch to
off, except if the unit is drained
Trane does not recommend draining the unit, due to
the fact that it increases corrosion
Seasonal start-up
Check water flows and interlocks
Check Ethylene glycol % in the chilled water circuit if
glycol presence is required
Check operational setpoints and performance
Calibrate controls
Check operation of all safety devices
Inspect contacts and tighten terminals.
Megger the motor compressor windings
Record operating pressures, temperatures, amperages
and voltage
Carry out leak test
Check configuration of unit control module
Change the oil as required based upon results of the
oil analysis made during seasonal shutdown Get the
8 condition easurements at the same time, on each
circuit
HP
LP
Suction temperature
Discharge temperature
Liquid temperature
Water entering temperature
Water leaving temperature
Outdoor ambient temperature Then calculate the sub-
cooling and superheat. No diagnosis can be accurate
with one of these recordsmissing
Check operation of machines/compare conditions of
operation against original commissioning data
Fill out the visit log sheet and review with the operator