CG-SVX027D-GB
5
11UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 55 50 42 37 37 31 30 46
FWD 08 2 57 54 47 40 30 38 40 50
3 58 57 50 42 32 40 43 53
1 57 51 45 42 34 33 28 48
FWD 10 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 57 51 45 42 34 33 28 48
FWD 12 2 58 54 48 45 38 39 35 51
3 60 58 50 48 40 42 39 54
1 56 62 50 48 39 38 36 56
FWD 14 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
1 57 63 51 49 40 39 37 57
FWD 20 2 61 66 55 53 47 46 45 60
3 63 69 58 56 50 50 49 63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan Power level in dB(A), per Hz frequency band Overall power
Unit speed 125 250 500 1000 2000 4000 8000 dB(A)
1 56 55 55 53 46 45 42 57
FWD 08 2 63 62 60 60 53 53 53 64
3 66 65 63 62 56 55 57 67
1 62 58 55 58 51 48 44 61
FWD 10 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 62 58 55 58 51 48 44 61
FWD 12 2 66 63 60 62 56 55 52 66
3 70 67 63 65 59 59 57 69
1 66 65 65 65 57 50 46 68
FWD 14 2 73 72 69 71 64 59 57 74
3 78 76 73 75 69 64 63 78
1 68 72 64 64 56 52 50 69
FWD 20 2 76 76 68 71 65 61 61 75
3 78 79 71 74 69 66 66 78
Model Number Description
Digit 1-4 — Chiller Model
CGAX = Cooling-only unit
CXAX = Heat pump unit
Digit 5-7 — Unit Nominal Tonnage
015
017
020
023
026
030
036
039
045
035
040
046
052
060
Digit 8 — Unit Voltage
E = 400V/3ph/50Hz
Digit 9 — Manufacturing Plant
1 = Europe
Digit 10-11 — Design Sequence
A = Factory asigned
0 = Factory asigned
Digit 12 — Efficiency Level
1 = Standard Efficiency (SE)
2 = High Efficiency (HE)
Digit 13 — Agency Listing
E = CE Certification
Digit 14 — Pressure Vessel Code
4 = Pressure Equipment Directive (PED)
Digit 15 — Condenser Temperature Range
A = Standard ambient (5°C/46°C)
C = Low ambient CGAX (-18°C/46°C) - CXAX cooling
mode (-10°C/46°C)
Digit 16, 17 — Open for future options
Digit 18 — Freeze Protection (Factory-Installed Only)
X = Without freeze protection
2 = With freeze protection by heaters
3 = With freeze protection by pump activation
Digit 19, 20 — Open for future options
Digit 21 — Evaporator Application
A = Comfort application (5°C/20°C)
B = Process application (CGAX: -12°C/5°C;
CXAX: -10°C/5°C)
Digit 22 — Evaporator Water Connection
1 = Grooved pipe
3 = Grooved pipe, couplings and pipe stub
Digit 23 — Condensor
B = Standard Aluminum Fin coil for CXAX
E = Epoxy Aluminum Fin coil for CGAX
H = MCHE for CGAX
J = E-coated MCHE for CGAX
Digit 24 — Heat Recovery
X = None
2 = Partial Heat Recovey
Digit 25 — Open for future options
Digit 26 — Starter Type
A = Across-the-line starter
B = Solid State Soft Starter
Digit 27, 28, 29 — Open for future options
Digit 30 — Human Interface
A = Standard Display
B = Deluxe Display
X = Without Display
Digit 31 — Communication Options
X = without remote communication
1 = Modbus Interface
2 = LonTalk Interface
4 = BACnet Interface
Digit 32 — Customer Input/Output extension module
X = None
A = With (1A4)