Start-Up
100 WSHP-SVX01Q-EN
GEH*/GEV*240 (60 Hz)
GEH*/GEV*180 (50 Hz)
68 60 129 - 148 237 - 301 9 - 12 23 - 29 129 - 149 309 - 394 7 - 9 34 - 42
GEH*/GEV*240 (60 Hz)
GEH*/GEV*180 (50 Hz)
77 40 131 - 150 294 - 374 15 - 19 22 - 28 135 - 156 315 - 400 11 - 14 34 - 43
GEH*/GEV*240 (60 Hz)
GEH*/GEV*180 (50 Hz)
77 60 130 - 150 275 - 350 10 - 12 22 - 28 144 - 166 322 - 409 8 - 10 36 - 45
GEH*/GEV*240 (60 Hz)
GEH*/GEV*180 (50 Hz)
86 40 132 - 152 325 - 414 14 - 17 22 - 28 159 - 183 334 - 425 12 - 16 37 - 47
GEH*/GEV*240 (60 Hz)
GEH*/GEV*180 (50 Hz)
86 60 132 - 152 308 - 392 9 - 12 22 - 28 170 - 196 342 - 436 9 - 11 39 - 49
GEH*/GEV*240 (60 Hz)
GEH*/GEV*180 (50 Hz)
95 40 134 - 154 367 - 467 13 - 17 22 - 27 — — — —
GEH*/GEV*240 (60 Hz)
GEH*/GEV*180 (50 Hz)
95 60 134 - 154 349 - 444 9 - 11 22 - 28 — — — —
GEH*/GEV*300 (60 Hz)
GEH*/GEV*240 (50 Hz)
32 50 — — — — 62 - 71 275 - 350 6 - 8 24 - 30
GEH*/GEV*300 (60 Hz)
GEH*/GEV*240 (50 Hz)
32 75 — — — — 65 - 75 279 - 355 4 - 6 25 - 31
GEH*/GEV*300 (60 Hz)
GEH*/GEV*240 (50 Hz)
45 50 120 - 138 181 - 231 15 - 19 22 - 28 80 - 92 291 - 370 8 - 10 26 - 33
GEH*/GEV*300 (60 Hz)
GEH*/GEV*240 (50 Hz)
45 75 119 - 137 169 - 215 10 - 13 22 - 28 84 - 97 295 - 376 5 - 7 27 - 34
GEH*/GEV*300 (60 Hz)
GEH*/GEV*240 (50 Hz)
55 50 121 - 140 209 - 267 14 - 18 22 - 28 96 - 111 309 - 394 8 - 11 29 - 36
GEH*/GEV*300 (60 Hz)
GEH*/GEV*240 (50 Hz)
55 75 121 - 139 196 - 249 10 - 12 22 - 28 102 - 117 314 - 399 6 - 8 30 - 37
GEH*/GEV*300 (60 Hz)
GEH*/GEV*240 (50 Hz)
68 50 124 - 142 251 - 320 14 - 18 22 - 27 119 - 137 330 - 420 10 - 13 32 - 40
GEH*/GEV*300 (60 Hz)
GEH*/GEV*240 (50 Hz)
68 75 123 - 142 236 - 301 9 - 12 22 - 27 127 - 146 335 - 427 7 - 9 33 - 42
GEH*/GEV*300 (60 Hz)
GEH*/GEV*240 (50 Hz)
77 50 126 - 145 289 - 368 15 - 18 21 - 27 133 - 153 342 - 435 11 - 14 34 - 43
GEH*/GEV*300 (60 Hz)
GEH*/GEV*240 (50 Hz)
77 75 125 - 144 272 - 346 10 - 12 21 - 27 142 - 163 348 - 443 8 - 10 35 - 45
GEH*/GEV*300 (60 Hz)
GEH*/GEV*240 (50 Hz)
86 50 127 - 147 319 - 406 13 - 17 21 - 27 156 - 180 362 - 461 13 - 16 37 - 46
GEH*/GEV*300 (60 Hz)
GEH*/GEV*240 (50 Hz)
86 75 127 - 146 302 - 385 9 - 11 21 - 27 168 - 193 371 - 472 9 - 11 39 - 49
GEH*/GEV*300 (60 Hz)
GEH*/GEV*240 (50 Hz)
95 50 130 - 149 357 - 454 13 - 17 21 - 26 — — — —
GEH*/GEV*300 (60 Hz)
GEH*/GEV*240 (50 Hz)
95 75 129 - 148 340 - 433 9 - 11 21 - 26 — — — —
Table 53. Operating pressures in cooling/heating for GE* units (continued)
Operating Data
Model No.
Entering
Water
Temp
(°F)
Water
Flow
(GPM)
Cooling Heating
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Rise
(°F)
Air Temp
Drop
(°F DB)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Drop
(°F)
Air
Temp
Rise
(°F DB)
Table 54. Operating pressures in cooling/heating for EX* units (60 Hz)
Operating Data
Cooling Heating
Model
Entering
water
temp (ºF)
Water
flow
(GPM)
Suction
pressure
(psig)
Discharge
pressure
(psig)
Water
temp rise
(ºF)
Air temp
drop
(ºF DB)
Suction
pressure
(psig)
Discharge
pressure
(psig)
Water
Temp drop
(ºF)
Air temp
rise
(ºF DB)
EXH*006 35 1.4 — — — — 94-108 279-355 6-8 23-29
EXH*006 35 1.7 — — — — 96-110 281-357 5-6 23-29