Unit Dimensions
WSHP-SVX01Q-EN 45
Figure 36. Waterside economizer
(a)
(GEH/EXH)
(a)Waterside economizer installation requires field piping.
H
M
5"
J
20"
N
G 1 1/2"
L
K
C
D
F
2 1/2"
E
TOP VIEW
FRONT VIEW
A = TO FIELD
SUPPLY PIPING
B = TO FIELD
RETURN PIPING
5/8”
5/8"
Table 26. Dimensional data waterside economizer (GEH/EXH)
GEH
(60 Hz)
GEH
(50 Hz) A NPTI B NPTI C D E F G H J K L M N
006-015 006-012 1/2 1/2 16-1/8 13-5/8 1-1/2 10-3/4 23 2-1/4 7-1/2 1/2 1 4 18-1/2
018-030 015-024 3/4 3/4 18-1/2 15-5/8 1-1/2 13-3/4 26 3-1/4 6-7/8 1/2 1 4 18-1/2
035-042 030-036 3/4 3/4 21 17-5/8 2-1/4 16-1/2 30 3-3/4 6-1/4 1-1/4 2 4-1/2 23-1/2
048-060 042-060 1 1 23-1/8 19-5/8 2-1/2 19-1/2 34 5-1/4 5-7/8 1-1/4 2 4-1/2 23-1/2
EXH
(60 Hz)
EXH
(50 Hz) A NPTI B NPTI C D E F G H J K L M N
006-015 1/2 1/2 16-1/8 13-5/8 1-1/2 10-3/4 23 2-1/4 7-1/2 1/2 1 4 18-1/2
018-024 3/4 3/4 18-1/2 15-5/8 1-1/2 13-3/4 26 3-1/4 6-7/8 1/2 1 4 18-1/2
030-036 3/4 3/4 21 17-5/8 2-1/4 16-1/2 30 3-3/4 6-1/4 1-1/4 2 4-1/2 23-1/2
042-070 1 1 23-1/8 19-5/8 2-1/2 19-1/2 34 5-1/4 5-7/8 1-1/4 2 4-1/2 23-1/2