Controls
CAB-PRC001-EN26
general
information
Table C-1. Tracer ZN controller input/output summary
Tracer controller ZN010 ZN510 ZN520
Binary Outputs
3-speed fan aaa
2-position hydronic valve aaa
2-position fresh air damper aa
1-stage electric heat aaa
3-wire hydronic valve a
2-stage electric heat a
generic aaa
Binary Inputs
occupancy aaa
generic input aaa
Analog Inputs
zone temperature aaa
detpoint aaa
fan mode: auto, high, medium, low aaa
entering water aaa
discharge air aaa
outside air a
generic a
Note: The generic input and output are for use with a Tracer Summit system only.
Table C-2. Tracer ZN controller function summary
ZN010 ZN510 ZN520
Control Functions
timed override aaa
fan cycling aa
warmup aaa
data sharing (master/slave) aa
random start aaa
staged capacity (2-stage electric supplementary) a
Other Functions
manual test aaa
maintenance timer aaa
setpoint limits aaa