RT-SVX096A-EN
11
Dimensional Data
Below figure illustrates the minimum operating and service
clearances for either a single or multiple unit installation.
These clearances are the minimum distances necessary to
assure adequate serviceability, cataloged unit capacity, and
peak operating efficiency.
Providing less than the recommended clearances may
result in condenser coil starvation, “short-circuiting” of
exhaust and economizer airflows, or recirculation of hot
condenser air.
WARNING
Airflow Obstruction!
Failure to follow instructions below could result in
death or serious injury or property damage.
Use the unit in well-ventilated spaces and ensure that
there are no obstructions that could impede the
airflow into and out of the unit. Do not use this unit in:
Locations with mineral oil, saline atmospheres
(seaside locations), sulfurous atmospheres (natural
hot springs), area with high voltage electricity
(industrial locations).
On vehicles or vessels, such as trucks or ferry
boats.
Areas exposed to oily or humid air, such as
kitchens.
In proximity to sources of electromagnetic
radiation, such as high-frequency transmitters or
other high strength radiation devices.