EasyManua.ls Logo

Trane GEH 006 - Page 28

Trane GEH 006
144 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
28 WSHP-PRC001-EN
Boiler/Cooling Tower Application
In a boiler/cooling tower application (Figure 37), the closed water-loop, along
with multiple water-source heat pumps are utilized in a more conventional
manner.
Typically, a boiler is used to maintain closed-loop temperatures
above 60 F, and a cooling tower is used to maintain
closed-loop temperature below 90 F. All the units
function independently, either by adding heat,
or rejecting heat, or moving heat from the
closed water-loop. Because the heat
from a building is being rejected
through a cooling tower, the system
is more efficient than air cooled sys-
tems.
The boiler/cooling tower system pro-
vides a low installation cost to the
owner when compared to other sys-
tems, and is the most common applica-
tion. It also allows the owner to add units to
the condenser water loop as needed.
Ground Coupled Application
Systems that utilize the ground-coupled (geothermal) design are also applied to
a closed water-loop, along with the multiple ground-source heat pumps.
With the ground-coupled (geothermal) system, heat is exchanged with the earth
by either moving heat into the earth, or absorbing heat from the earth. Water
temperature ranges vary from 25 F to 105 F depending on climate, and season.
Because the ground-coupled system does not use the fluctuating outside-air
temperature, the geothermal heat pumps are capable of using less energy.
The choices in earth-loop coupling consists of a vertical (Figure 38), hor-
izontal, or a pond-loop design. Each of these options offer different
system design characteristics. The vertical and horizontal loop
systems can be designed to provide the same fluid temper-
atures under a given set of conditions.
Operating and maintenance cost are lower
because an auxiliary electric/fossil fuel
boiler and cooling tower are not re-
quired to maintain the loop tempera-
ture in a properly designed system.
Because the ground loop is made of
chemically inert, non-polluting, high
density polyethylene pipe, the loop
is environmentally responsible. The
heat pumps use HCFC-22 refrigerant,
which has a low ozone depletion poten-
tial. Because the closed-loop system does
not require a heat adder, there are no C02 emis-
sions. Less power is consumed by the system, thereby
reducing secondary emissions from the power plant. Therefore, the
ground-coupled system offers advantages not seen by other HVAC system types.
Application
Considerations
Figure 37: Boiler/cooling tower
Figure 38: Vertical bore ground loop
application
application

Related product manuals