WSHP-PRC001-EN 61
Performance Data
024-Heating
Table P18: GEH/GEV 024 Heating Performance
Performance data is tabulated for heating at 68 F DB entering air at ARI/ISO 13256-1 rated CFM.
For conditions other than what is tabulated, multipliers must be used to correct performance. See the fan correction factors Table for CFM
other than rated and the heating correction factors for variations in entering air temperature. Data shown in bold type is performance data
at ARI/ISO 13256-1 WLHP and GLHP water only conditions. Antifreeze correction factors may be found on page 108.
RATED GPM: 5.5 MINIMUM CFM: 608
RATED CFM: 760 MAXIMUM CFM: 912
EWT GPM Htg Cap
Mbtuh
Absorb
Mbtuh
Power
kW
LWT Ft.
Hd.
CFM ISO Cap
Mbtuh
ISO Pwr
kW
ISO
COP
25
3.6 16.1 10.7 1.59 19.1 5.8
760
15.5 1.43 3.2
4.4 16.5 11.0 1.61 20.0 7.8 15.9 1.46 3.2
5.0 16.8 11.3 1.62 20.5 9.4 16.2 1.48 3.2
5.5 17.0 11.4 1.63 20.9 10.7 16.4 1.49 3.2
5.8 17.1 11.5 1.63 21.0 11.6 16.5 1.50 3.2
6.1 17.2 11.6 1.64 21.2 12.5 16.6 1.51 3.2
6.6 17.4 11.8 1.64 21.4 14.0 16.8 1.52 3.2
GLHP
32
3.6 18.5 12.7 1.70 24.9 4.9
760
17.9 1.54 3.4
4.4 19.0 13.1 1.72 26.0 6.9 18.4 1.57 3.4
5.0 19.2 13.3 1.73 26.7 8.4 18.6 1.58 3.5
5.5 19.4 13.5 1.74 27.1 9.7 18.8 1.60 3.4
5.8 19.5 13.6 1.74 27.3 10.6 18.9 1.61 3.4
6.1 19.6 13.6 1.75 27.5 11.4 19.0 1.62 3.4
6.6 19.7 13.8 1.75 27.8 12.9 19.2 1.63 3.5
45
3.6 22.8 16.5 1.85 35.8 5.0
760
22.2 1.69 3.8
4.4 23.4 17.0 1.87 37.3 6.8 22.8 1.72 3.9
5.0 23.6 17.2 1.88 38.1 8.2 23.0 1.73 3.9
5.5 23.8 17.3 1.89 38.7 9.4 23.2 1.75 3.9
5.8 23.9 17.4 1.89 39.0 10.2 23.3 1.75 3.9
6.1 24.0 17.5 1.90 39.3 11.0 23.4 1.77 3.9
6.6 24.2 17.7 1.90 39.6 12.3 23.6 1.78 3.9
55
3.6 26.1 19.3 1.98 44.3 4.7
760
25.5 1.82 4.1
4.4 26.7 19.9 2.00 46.0 6.3 26.1 1.84 4.2
5.0 27.0 20.1 2.01 47.0 7.7 26.4 1.86 4.2
5.5 27.2 20.3 2.02 47.6 8.8 26.6 1.88 4.1
5.8 27.3 20.4 2.03 48.0 9.6 26.7 1.89 4.1
6.1 27.4 20.5 2.03 48.3 10.3 26.8 1.90 4.1
6.6 27.5 20.5 2.04 48.8 11.6 26.9 1.92 4.1
WLHP
68
3.6 29.9 22.6 2.14 55.4 4.3
760
29.3 1.98 4.3
4.4 30.5 23.1 2.16 57.5 5.8 29.9 2.00 4.4
5.0 30.8 23.4 2.17 58.6 7.1 30.2 2.02 4.4
5.5 31.0 23.6 2.18 59.4 8.1 30.4 2.04 4.4
5.8 31.1 23.7 2.18 59.8 8.8 30.5 2.04 4.4
6.1 31.2 23.7 2.19 60.2 9.5 30.6 2.05 4.4
6.6 31.4 23.9 2.19 60.7 10.8 30.8 2.06 4.4
75
3.6 31.7 24.2 2.19 61.5 4.1
760
31.1 2.03 4.5
4.4 32.3 24.8 2.21 63.7 5.6 31.7 2.05 4.5
5.0 32.6 25.0 2.22 65.0 6.8 32.0 2.07 4.5
5.5 32.8 25.2 2.23 65.8 7.8 32.2 2.08 4.5
5.8 32.9 25.3 2.24 66.3 8.5 32.3 2.10 4.5
6.1 33.0 25.4 2.24 66.7 9.2 32.4 2.10 4.5
6.6 33.2 25.5 2.25 67.3 10.3 32.6 2.12 4.5
86
3.6 34.1 26.3 2.29 71.3 3.8
760
33.5 2.13 4.6
4.4 34.8 26.9 2.31 73.7 5.2 34.2 2.15 4.7
5.0 35.1 27.2 2.32 75.1 6.3 34.5 2.17 4.7
5.5 35.3 27.3 2.33 76.0 7.3 34.7 2.18 4.7
5.8 35.4 27.4 2.34 76.5 8.0 34.8 2.20 4.6
6.1 35.5 27.5 2.34 76.9 8.6 34.9 2.20 4.6
6.6 35.6 27.6 2.35 77.6 9.8 35.0 2.22 4.6
Table P19: 024 Fan Correction Factors
Entering
CFM
Cooling
Capacity
Sensible
Capacity
Cooling
Input
Watts
Heating
Capacity
Heating
Input
Watts
608 0.974 0.892 0.965 0.972 1.032
646 0.980 0.919 0.973 0.979 1.024
684 0.987 0.945 0.981 0.986 1.016
722 0.993 0.972 0.990 0.993 1.008
760 1.000 1.000 1.000 1.000 1.000
836 1.012 1.051 1.020 1.013 0.984
874 1.019 1.078 1.030 1.020 0.976
912 1.025 1.105 1.042 1.027 0.968