WSHP-PRC001-EN 79
Performance Data
240-Heating
Table P-47: GEV 240 Heating Performance
Performance data is tabulated for heating at 68 F DB entering air at ARI/ISO 13256-1 rated CFM.
For conditions other than what is tabulated, multipliers must be used to correct performance. See the fan correction factors Table for CFM
other than rated and the heating correction factors for variations in entering air temperature. Data shown in bold type is performance data
at ARI/ISO 13256-1 WLHP and GLHP water only conditions. Antifreeze correction factors may be found on page 108.
RATED ESP (in. H20): 0.40 RATED GPM: 60.0 MINIMUM CFM: 6400
RATED CFM: 8000 MAXIMUM CFM: 9600
EWT GPM Htg Cap
Mbtuh
Absorb
Mbtuh
Power
kW
LWT Feet
Head
PSID
Head
SCFM ISO Cap
Mbtuh
ISO
Power
kW
ISO COP
25
30.0 168.4 112.6 16.34 17.5 4.2 1.81
8000
164.2 15.16 3.17
40.0 171.9 115.8 16.43 19.2 7.0 3.05 167.6 15.35 3.20
50.0 174.5 118.2 16.50 20.3 10.6 4.57 170.3 15.58 3.20
60.0 176.7 120.2 16.56 21.0 14.7 6.36 172.4 15.86 3.19
70.0 178.5 121.8 16.60 21.5 19.4 8.42 174.2 16.20 3.15
GLHP
32
30.0 182.7 125.6 16.72 23.6 4.2 1.81
8000
178.4 15.54 3.36
40.0 186.6 129.2 16.82 25.5 7.0 3.05 182.4 15.74 3.39
50.0 189.7 132 16.90 26.7 10.6 4.57 185.5 15.98 3.40
60.0 192.2 134.3 16.97 27.5 14.7 6.36 188.0 16.27 3.39
70.0 194.3 136.2 17.03 28.1 19.4 8.42 190.0 16.63 3.35
45
30.0 210.4 150.8 17.46 34.9 4.2 1.81
8000
206.2 16.29 3.71
40.0 215.5 155.4 17.60 37.2 7.0 3.05 211.2 16.53 3.75
50.0 220.7 160.2 17.74 38.6 10.6 4.57 216.4 16.82 3.77
60.0 223.9 163 17.83 39.6 14.7 6.36 219.6 17.13 3.76
70.0 225.3 164.3 17.87 40.3 19.4 8.42 221.1 17.48 3.71
55
30.0 232.9 171.2 18.08 43.6 4.2 1.81
8000
228.6 16.91 3.96
40.0 238.8 176.5 18.25 46.2 7.0 3.05 234.6 17.17 4.00
50.0 243.6 180.9 18.38 47.8 10.5 4.57 239.3 17.46 4.02
60.0 247.4 184.3 18.49 48.9 14.7 6.36 243.1 17.79 4.01
70.0 250.6 187.2 18.58 49.6 19.4 8.41 246.3 18.18 3.97
WLHP
68
30.0 263.3 198.7 18.93 54.7 4.2 1.80
8000
259.0 17.76 4.28
40.0 270.6 205.3 19.14 57.7 7.0 3.04 266.3 18.06 4.32
50.0 276.4 210.5 19.30 59.6 10.5 4.56 272.1 18.38 4.34
60.0 281.1 214.8 19.44 60.8 14.7 6.35 276.8 18.74 4.33
70.0 285.0 218.3 19.55 61.8 19.4 8.40 280.7 19.15 4.30
75
30.0 280.3 214.1 19.41 60.7 4.2 1.80
8000
276.0 18.24 4.44
40.0 288.4 221.4 19.64 63.9 7.0 3.04 284.1 18.57 4.48
50.0 294.8 227.1 19.83 65.9 10.5 4.55 290.5 18.91 4.50
60.0 300.0 231.8 19.98 67.3 14.6 6.34 295.8 19.28 4.50
70.0 304.4 235.8 20.11 68.2 19.4 8.38 300.1 19.70 4.46
86
30.0 307.8 238.8 20.21 70.0 4.1 1.79
8000
303.6 19.03 4.68
40.0 317.2 247.3 20.48 73.6 7.0 3.03 313.0 19.40 4.73
50.0 324.7 254.1 20.70 75.8 10.5 4.54 320.4 19.77 4.75
60.0 330.8 259.6 20.87 77.3 14.6 6.32 326.5 20.17 4.74
70.0 335.9 264.2 21.02 78.4 19.3 8.36 331.6 20.62 4.71
Table P48: 240 Correction Factor for Variation in Entering Air Temperature
Cooling
Entering
Air WB F
Cooling
Capacity
Cooling
Input
Watts
Sensible vs Entering Dry Bulb
Multipliers
Heating
Entering
Air DB F
Heating
Capacity
Heating
Input
Watts
65.6 70.6 75.6 80.6 85.6
49.4 0.916 0.985 1.016 1.082 1.148 1.215 1.282 53.0 1.027 0.892
56.3 0.918 0.985 0.815 1.005 1.150 1.217 1.284 58.0 1.018 0.925
60.3 0.919 0.985 0.659 0.852 1.041 1.218 1.285 63.0 1.009 0.962
63.2 0.952 0.992 0.543 0.738 0.929 1.118 1.286 68.0 1.000 1.000
66.2 1.000 1.000 0.615 0.810 1.000 1.190 73.0 0.992 1.041
72.1 1.102 1.015 0.566 0.761 0.956 78.0 0.985 1.085
77.1 1.191 1.025 0.550 0.746 83.0 0.977 1.132
Table P49: 240 Fan Correction Factors
Entering
SCFM
Cooling
Capacity
Sensible
Capacity
Cooling
Input
Watts
Heating
Capacity
Heating
Input
Watts
6400 0.963 0.901 0.994 0.990 1.059
7200 0.983 0.952 0.997 0.995 1.026
8000 1.000 1.000 1.000 1.000 1.000
8800 1.014 1.047 1.002 1.004 0.980
9600 1.026 1.091 1.004 1.007 0.963