100
WSHP-SVX01AA-EN
Table 54. Operating pressures in cooling/heating for GE units (continued)
Operating Data
Model
Entering
Water
Temp
F)
Water
Flow
(GPM)
Cooling Heating
Suction
Pressure
(psig)
Dis-
charge
Pressure
(pgig)
Water
Temp
Rise (°F)
Air Temp
Drop (°F
DB)
Suction
Pressure
(psig)
Dis-
charge
Pressure
(psig)
Water
Temp
Drop
F)
Air Temp
Rise (°F
DB)
GEVG036 (60 Hz)
86 7.20 137-158 319-406 11-14 21-26 182-209 387-493 10-13 37-48
GEVG036 (60 Hz)
86 9.00 137-158 312-397 9-11 21-26 187-215 391-498 8-11 37-48
GEVG036 (60 Hz)
95 7.20 139-160 358-455 11-14 20-26
GEVG036 (60 Hz)
95 9.00 139-160 350-446 9-11 20-26
GEHE042 (60 Hz)
GEHE036 (50 Hz)
35 7.80 74-86 269-342 6-7 20-30
GEHE042 (60 Hz)
GEHE036 (50 Hz)
35 9.80 76-87 270-344 5-6 21-30
GEHE042 (60 Hz)
GEHE036 (50 Hz)
45 7.80 116-134 173-220 12-16 21-27 86-99 281-358 7-8 23-33
GEHE042 (60 Hz)
GEHE036 (50 Hz)
45 9.80 116-134 167-212 10-13 21-27 88-101 283-360 5-7 24-33
GEHE042 (60 Hz)
GEHE036 (50 Hz)
55 7.80 118-135 201-256 12-15 21-26 102-118 298-379 8-10 27-36
GEHE042 (60 Hz)
GEHE036 (50 Hz)
55 9.80 118-135 194-247 10-12 21-26 105-121 300-382 6-8 27-37
GEHE042 (60 Hz)
GEHE036 (50 Hz)
68 7.80 122-140 242-308 12-15 20-26 121-140 317-403 9-11 31-41
GEHE042 (60 Hz)
GEHE036 (50 Hz)
68 9.80 121-140 235-299 10-12 21-26 125-144 321-408 7-9 31-42
GEHE042 (60 Hz)
GEHE036 (50 Hz)
75 7.80 123-141 267-340 12-15 20-26 135-156 331-422 10-12 33-44
GEHE042 (60 Hz)
GEHE036 (50 Hz)
75 9.80 123-141 259-330 9-12 20-26 140-161 336-427 8-10 34-45
GEHE042 (60 Hz)
GEHE036 (50 Hz)
86 7.80 125-144 308-392 12-15 20-25 159-183 355-451 11-14 38-49
GEHE042 (60 Hz)
GEHE036 (50 Hz)
86 9.80 125-144 300-382 9-12 20-26 165-190 359-457 9-12 39-50
GEHE042 (60 Hz)
GEHE036 (50 Hz)
95 7.80 127-146 346-441 11-15 19-25
GEHE042 (60 Hz)
GEHE036 (50 Hz)
95 9.80 127-146 338-430 9-12 19-25
GEVG042 (60 Hz)
32 8.40 88-101 309-393 5-6 18-28
GEVG042 (60 Hz)
32 10.50 90-103 311-395 4-5 19-28
GEVG042 (60 Hz)
45 8.40 125-144 179-228 11-15 22-27 106-122 334-425 6-8 23-33
GEVG042 (60 Hz)
45 10.50 125-144 174-221 9-12 22-27 109-125 337-429 5-7 24-33
GEVG042 (60 Hz)
55 8.40 127-146 207-263 11-14 21-27 122-140 355-451 7-9 27-37
GEVG042 (60 Hz)
55 10.50 127-146 200-255 9-11 21-27 125-144 358-456 6-8 27-37