EasyManua.ls Logo

Trane GEVE - Wiring Diagrams

Trane GEVE
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
114
WSHP-SVX01AA-EN
Table 61. Troubleshooting table (continued)
Problem
Hea-
ting
Cool-
ing
Cause Correction
High head pressure
X
Trash in heat exchanger
Backflush
X Low water flow Increase GPM
X X
Overcharge of refrigerant Decrease charge
X X
Non-condensable in system Evacuate and recharge by weight
X X Water too hot
Decrease temperature
X
Dirty filter Clean / replace
X
Inadequate air flow Check, clean blower and coil
Low suction pressure
X X
Undercharged Locate leak, repair and recharge
X X
Restricted thermal expansion valve Repair / replace
X
Inadequate air flow Check, clean blower and coil
X
Dirty filter Clean/replace
X
Inadequate GPM
Increase GPM
Low pressure switch open
X
Inadequate GPM
Increase GPM
X Water too cold
Increase temperature
X
Inadequate air flow
Increase CFM
X
Dirty filter Clean/replace
X X
Undercharged with refrigerant Increase charge
X X
Defective pressure switch Replace
X X Heat transfer fluid too cold
Raise water temperature
TTrroouubblleesshhoooottiinngg