SSAAFFEETTYY WWAARRNNIINNGG
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning
equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person
could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that
are attached to the equipment.
November 2021
WWSSHHPP--SSVVXX0011AAAA--EENN
Installation, Operation, and Maintenance
Water Source Heat Pump
Axiom Horizontal/Vertical
GEH/V*
0.5 to 25 Tons, 50/60 Hz
Model Numbers:
GEHE 006-060 - 50/60 Hz
GEVG 006-060 - 60 Hz
GEHE 072-180 - 50/60 Hz
GEVE 072-300 - 50/60 Hz

Table of Contents

Other manuals for Trane GEVE

Questions and Answers

  • R
    Renee JohnsonAug 12, 2025
    What to do if my Trane GEVE Heat Pump has no response to thermostat settings?
    • K
      Kelly MedinaAug 12, 2025
      If your Trane Heat Pump isn't responding to thermostat settings, the possible causes include: the main power being off (check fuses), a defective control transformer (replace it), broken or loose connections (repair them), a defective thermostat (replace it), or a transformer issue (reset the transformer).
  • C
    Carla ChavezAug 16, 2025
    What to do if my Trane Heat Pump compressor does not run, but the blower does?
    • J
      Jamie JonesAug 16, 2025
      If the blower runs but the compressor doesn't in your Trane Heat Pump, it could be due to a defective compressor overload (replace if external), a defective compressor contactor (replace it), supply voltage being too low (correct it), a defective compressor capacitor (replace it), defective windings (replace them), or limit switches being open (check cause/replace or repair).
  • D
    dsuttonAug 19, 2025
    What to do if my Trane Heat Pump unit short cycles?
    • C
      Carrie CooperAug 19, 2025
      If your Trane Heat Pump is short cycling, it may be because the thermostat or sensor is improperly located. If this is the case, relocate them.
  • S
    Susan WilsonAug 23, 2025
    Why is my Trane GEVE Heat Pump not providing enough capacity?
    • B
      Brianna MillerAug 23, 2025
      Insufficient capacity in your Trane Heat Pump can stem from several issues: a dirty filter (replace or clean it), blower RPM being too low (correct it), leaks in the ductwork (repair them), introduction of excessively hot or cold return-air (correct this), low refrigerant charge (locate the leak, repair, and recharge), a restricted thermal expansion valve (replace it), a defective reversing valve, an improperly located thermostat (relocate it), an undersized unit (recalculate heat gains/losses), inadequate water flow (increase GPM), scaling in the heat exchanger (clean or replace it), water being too hot or too cold (adjust the temperature), or a blocked filter drier (replace it).
  • W
    William ChavezAug 27, 2025
    Why does my Trane Heat Pump have high head pressure?
    • D
      Dr. Manuel CallahanAug 27, 2025
      High head pressure in your Trane Heat Pump may be due to trash in the heat exchanger (backflush it), low water flow (increase GPM), an overcharge of refrigerant (decrease the charge), non-condensables in the system (evacuate and recharge by weight), water being too hot (decrease the temperature), a dirty filter (clean or replace it), or inadequate air flow (check and clean the blower and coil).
  • R
    Robert TurnerAug 31, 2025
    Why is the high pressure switch open on my Trane GEVE?
    • M
      Miranda ButlerAug 31, 2025
      If the high pressure switch is open on your Trane Heat Pump, possible causes include inadequate GPM (increase water flow to unit), water being too hot (decrease temperature), inadequate air flow (check and clean blower and coil), a dirty filter (clean/replace), being overcharged with refrigerant (decrease charge), or a defective pressure switch (check or replace).
  • G
    Glenn HobbsSep 4, 2025
    Why is the low pressure switch open on my Trane Heat Pump?
    • I
      iloveSep 4, 2025
      If the low pressure switch is open on your Trane Heat Pump, it could be due to inadequate GPM (increase GPM), water being too cold (increase temperature), inadequate air flow (increase CFM), a dirty filter (clean/replace), being undercharged with refrigerant (increase charge), a defective pressure switch (replace it), or the heat transfer fluid being too cold (raise water temperature).
  • Y
    ygilesSep 7, 2025
    Why does my Trane GEVE have low suction pressure?
    • E
      eobrienSep 7, 2025
      Low suction pressure in your Trane Heat Pump can be caused by being undercharged (locate leak, repair and recharge), a restricted thermal expansion valve (repair / replace), inadequate air flow (check, clean blower and coil), a dirty filter (clean/replace), or inadequate GPM (increase GPM).