7
-
Electrical
Cabinet
Low
Voltage
Sect
High
Voltag
e
Sec
I
L
Locate
line
voltage
disconnect
box
per
local
codes.
If
mounting
the
disconnect
box
to
the
unit,
never
mount
it
to
an
unit
access
panel.
Possible
locations
include
the
front
of
the
blower
or
filter
section,
the
outdoor
air
hood
or
the
rear
of
the
supply
plenum
(See
Figure
8).
Electrical
conduit
must
be
routed
so
as
not
to
inter-
fere
with
removal
of
any
access
panel.
NOTE
:
Should
any
or
i
g
i
nal
wire
suppl
i
ed
with
the
unit
hav
e
to
be
replaced
,
it
must
b
e
replaced
w
i
th
w
iri
ng
h
a
v
i
ng
a
temp
e
rature
r
a
t
i
ng
of
at
least
105
°
C
(221
°
F)
.
DX
COIL
EQU
I
PPED
UNITS (OPTIONAL)
See
Coil
Installation/Maintenance
Manual
for
Refrigerant
Piping,
Liquid
and
Suction
Line
Components,
Refrigerant
Charging
and
Thermal
Expansion
Valve
Adjustment.
Remove
piping
plate
located
in
lower
corner
next
to
filter
section
and
cut
holes
in
plate
to
allow
suction
and
liquid line
pas-
sage.
Provide
weatherproof
seal
around'suction
and
liquid
lines
at
piping
plate
when
installed.
The
DX
Coil
has
a
300
ft/min.
(1.524
m/s)
minimum
and
a
600
ft/min.
(3.048'
m/s)
maximum
velocity
through
the
coil
requirement.
This
is
due
to
preven-
tion
of
coil
icing
or
condensate
blow-off.
To
calculate
the
velocity
through
the
coil,
apply
the
following
for-
mula:
Velocity
Cooling
Air
Flow
in
CFM
(m3/s)
through
the
coil
^
Coil
Surface
Area
in
ft2
(m2)
opt
i
o
n
al
C
o
nt
rol
s
Jo
u
n
ci
ng
Locat
io
n
1Q
Back
Panel
OZ
main
connection
Board
Q
High
Voltage
Barrier
Assy
O4
24V
Transformer
Q5
High
Voltage
Terminal
Block
O8
Ground
Lug
O7
Din
Mounting
Rail
Contactor
or
Starter
1
D3
88
3
S
-
uisconnect
tJox
vocations
Di
s
conn
e
ct
9
D
i
scon
n
e
c
t
B
o
x
Located
On
Int
ake
E
n d
Pane
l
(Ret
ur
n
A
i
r
O
nl
y)
D
(acann
e
et
B
ox
Locat
ed
On
Out
s id
e
A
ir
Hood
iii
S
U
PP
L
Y
AIR
Disconnect
Bo
x
Locat
e
d
On
Supply
Pl
e
num
End
Pan
e
l
D3-9-6-6
Condensate
Drain
piping
must
have
a
P-trap
in
line
immediately
downstream
of
drain
pan
connection,
external
to
the
unit,
to
prevent
possible
outside
air
-10-