6
8
44
-101H
-/
leakage
into
unit.
The
P-trap
shall
be
of
sufficient
dif-
ferential
to
overcome
negative
pressure
of
the
indoor
air
blower.
A
minimum
height
difference
of
2"
is
required
(See
Figure
9).
Before
unit
operation
begins,
the
P-trap
must
be
primed
with
either
water
(summer)
or
glycol
(winter).
CHILLED
WATER
CO
I
L
EQU
I
PP
E
D
UN
I
TS
(
OP
TI
ONAL
)
See
Coil
Installation/Maintenance
Manual
for
General
Coil
Piping
Recommendations.
Remove
pip-
ing
plate
located
in
the
near
center
of
the
coil
cabinet
and
cut
holes
in
plate
to
allow
chilled
water
piping
passage.
Provide
weatherproof
seal
around
chilled
water
pipes
at
piping
plate
when
installed.
Figure
9
-
Drain
Pan
Connection
DRAIN
PAN
CONNECTION
UNIT
2
"
MIN
.
D3Bb7
The
Chilled
Water
Coil
has
a
600
ft/min
(3.048 m/s)
maximum
velocity
through
the
coil
requirement.
This
is
due
to
prevention
of
condensate
blow-off.
To
cal-
culate
the
velocity
through
the
coil
apply
the
follow-
ing
formula:
Velocity
Cooling
Air
Flow
in
CFM
(m3/s)
through
the
coil
Coil
Surface
Area
in
ft2
(m2)
Condensate
Drain
piping
must
have
a
P-trap
in
line
immediately
downstream
of
drain
pan
connection,
external
to
the
unit,
to
prevent
possible
outside
air
leakage
into
unit.
The
P-trap
shall
be
of
sufficient
dif-
ferential
to
overcome
negative
pressure
of
the
indoor
air
blower.
A
minimum
height
difference
of
2"
is
required
(See
Figure
9).
Before
unit
operation
begins,
prime
P-trap
with
either
water
(summer)
or
glycol
(winter).
EVAPORATIVE
COOLER
EQUIPPED
UNITS
(OPTIONAL)
Refer
to
Evaporative
Cooler
Installation
and
Service
Manual
for
water
and
electrical
connections.
IV
.
OPERATION
GENERAL
INFORMATION
Refer
to
Outdoor
Rooftop
Gas-Fired
Duct
Furnace
Installation
and
Service
Manual
for
specific
informa-
tion
regarding
the
heating
operation
of
this
unit.
All
units
are
equipped
with
a
intermittent
ignition
pilot
system.
The
pilot
is
lit
and
extinguished
each
cycle
of
unit
heating
operation.
Outlet
mu
s
t
be
b
e
low
u
ni
t
co
nne
c
t
ion
The
lockout
function
shuts
off
the
main
and
pilot
gas
valves
if
the
pilot
gas
fails
to
ignite
within
90
seconds
of
the
onset
of
trial
for ignition.
In
order
to
initiate
a
re-
ignition
trial,
the
power
supply
must
be
interrupted
for
30
seconds.
The
gas
control
system
operates
at
24
VAC
and
is
supplied
by
a
stepdown
transformer
found
in
the
electrical
cabinet
that
will
match
the
unit
line
voltage
specified.
See
Figure
6
for
unit
controls
location.
Do
not
use
a
thermostatic
fan
control
switch
when
either
two-stage
firing
or
modulated
gas
controls
are
used.
NOTE
:
Electronic
modulating
gas
controls
are
available
on
natural
gas
units
only
.
These
con-
trols
are
not
ava
i
lable
with
propane
units
.
GAS
CONTROL
SYST
E
M
The
standard
unit
comes
equipped
for
single
stage
operation.
Unit
heating
operation
is
accomplished
at
full
input.
Each
duct
furnace
is
equipped
with
an
individual
igni-
tion
control
system
which
consists
of
the
following
components:
ignition
control
module,
gas
valve
and
pilot
burner.
The
ignition
control
module
is
the
heart
of
the
igni-
tion
control
system.
This
control
initiates
all
gas
flow,
provides
means
to
light
the
pilot
burner,
proves
and
monitors
the
pilot
burner
operation.
The
gas
valve
consists
of
two
operators
which
pro-
vide
gas
to
the
pilot
and
main
burners.
Both
opera-
tors
are
energized
and
de-energized
by
the
ignition
control
module
each
heating
cycle.
On
natural
gas
units,
the
ignitor
will
continue
to
spark
and
pilot
gas
will
continue
to
flow
until
the
pilot
flame
The
pilot
burner
includes
an
ignitor
and
flame
sense
is
proven.
probe.
The
ignitor
provides
the
spark,
originating
at
the
ignition
control
module,
to
light
the
pilot.
The
igni-
LP
(propane)
units
are
equipped
with
100%
lockout.
tion
control
module
proves
and
monitors
the
pilot
flame
through
the
flame
sensing
probe.
-
11
-