Installation of refrigerant pipe
Concentrated drainage
Please select the drainage pipe with a diameter adapting to the running capacity of the unit.
Without drainage pump:
≥100
Indoor unit Indoor unit Indoor unit
Ceiling
Concentrated drainage pipe,
gradient ≥ 1/100
(Slim line) Duct type
With drainage pump:
When 3 or more indoor units are installed, a main air vent is provided for the indoor unit having a
farthest distance from the main drainage pipe.
Suspension
Main air vent
Concentrated drainage pipe,
gradient ≥ 1/100
1
~
1.5m
Indoor unit
Indoor unitIndoor unit
Ceiling
≤500
Main drainage
Drainage testing
Check the smoothness of drain after installation. Check the drain state by fi lling about 2 L water
into the drain pan of the indoor unit as shown in the following fi gure;
Set up the model of the drainage pump, run the unit in cooling mode, and check pumping;
Check the drain at the end of the drainage pipe. Make sure that the condensate water drains
smoothly, and no water leakage exists.
After completion of testing, insulate the condensate pipe.
Drainage
pipe
18 AMS-SVX04A-EN