Description of controller
System parameter query list
Press the Sleep button for 5s, the buzzer gives a sound, enter the query mode, the query address
is displayed in the temperature display area, the clock indicates the parameter, press Đ
▲
đor Đ
▼
đ
once, and the query address is switched once. If no operation is executed, quit the query mode
automatically.
Attached list: parameter query
Address code Parameter enquired Unit
00 Last fault code of system
01 Set address of indoor unit
02 Capacity of indoor unit kW
03 Indoor unit coil inlet temperature (T2) ņ
04 Indoor unit coil midpoint temperature (T3) ņ
05 Indoor unit coil outlet temperature (T4) ņ
06 Indoor return air temperature (T1) ņ
07 Opening of indoor unit EXV
08 Capacity of outdoor unit kW
09 Operating frequency of VF compressor HZ
10 Opening of outdoor unit EXV
11 Operating current of VF compressor A
12 Input voltage of outdoor unit V
13 Input current of outdoor unit A
14 VF compressor exhaust temperature (T9) ņ
15 VF compressor suction temperature (T10) ņ
16 Condenser inlet temperature (T6) ņ
17 Condenser midpoint temperature (T7) ņ
18 Outdoor ambient temperature (T5) ņ
19 Temperature of VF module radiator ņ
AMS-SVX04A-EN 25