26
SS-SVX001A-EN
Charging Levels
IImmppoorrttaanntt:: For the correct line diameter, for line
lengths greater than 25 feet, see the
Odyssey Application Guide (SS-APG008*-
EN) available through e-Library or your
local sales office.
Table 6. Estimated charge levels at AHRI rated line lengths (25 feet) - 50 & 60 Hz
Matched Set
Refrigerant Charge
Per Circuit
Circuit 1 Circuit 2
Liquid Line Diameter Vapor Line Diameter
TTA0604DA w/ TWE0764DA
10.0
N/A
0.5 (1/2”) 1.125 (1 1/8”)
TTA0604DD w/ TWE0724DB
7.0 7.0
0.5 (1/2”) 0.875 (7/8")
TTA0724*A w/ TWE0904*A
10.0
N/A
0.5 (1/2”) 1.125 (1 1/8”)
TTA0724*D w/ TWE0724*B
7.0 7.0
0.5 (1/2”) 0.875 (7/8")
TTA0764DA w/ TWE0764DA
9.7
N/A
0.5 (1/2”) 1.375 (1 3/8”)
TTA0764DA w/ TWE1014DA
9.5
N/A
0.5 (1/2”) 1.375 (1 3/8”)
TTA0764DD w/ TWE0764DB
7.3 7.3
0.5 (1/2”) 1.125 (1 1/8”)
TTA0904*A w/ TWE0904*A
9.7
N/A
0.5 (1/2”) 1.375 (1 3/8”)
TTA0904*A w/ TWE1204*A
9.5
N/A
0.5 (1/2”) 1.375 (1 3/8”)
TTA0904*D w/ TWE0904*B
7.3 7.3
0.5 (1/2”) 1.125 (1 1/8”)
TTA1014DD w/ TWE1014DB
7.6 7.6
0.5 (1/2”) 1.125 (1 1/8”)
TTA1014DC w/ TWE1014DA
13.1
N/A
0.5 (1/2”) 1.375 (1 3/8”)
TTA1204*D w/ TWE1204*B
8.2 8.4
0.5 (1/2”) 1.125 (1 1/8”)
TTA1204*C w/ TWE1204*A
13.1
N/A
0.5 (1/2”) 1.375 (1 3/8”)
TTA1264DD w/ TWE1264DB
9.7 9.7
0.5 (1/2”) 1.125 (1 1/8”)
TTA1504*D w/ TWE1504*B
9.8 9.8
0.5 (1/2”) 1.125 (1 1/8”)
TTA1564DD w/ TWE1564DB
11.5 11.5
0.5 (1/2”) 1.375 (1 3/8”)
TTA1564DD w/ TWE2014DB
9.2 9.4
0.5 (1/2”) 1.375 (1 3/8”)
TTA1564DC w/ TWE1564DB
21.4
N/A
0.625 (5/8”) 1.625 (1 5/8”)
TTA1804*D w/ TWE1804*B
11.5 11.5
0.5 (1/2”) 1.375 (1 3/8”)
TTA1804*D w/ TWE2404*B
9.2 9.3
0.5 (1/2”) 1.375 (1 3/8”)
TTA1804*C w/ TWE1804*B
22.5
N/A
0.625 (5/8”) 1.625 (1 5/8”)
TTA2014DD w/ TWE2014DB
11.6 12.3
0.5 (1/2”) 1.375 (1 3/8”)
TTA2014DC w/ TWE2014DB
23.8
N/A
0.625 (5/8”) 1.625 (1 5/8”)
TTA2404*D w/ TWE2404*B
11.2 11.2
0.5 (1/2”) 1.375 (1 3/8”)
TTA2404*C w/ TWE2404*B
23.8
N/A
0.625 (5/8”) 1.625 (1 5/8”)
TTA2514DC w/ TWE2514DB
29.8
N/A
0.625 (5/8”) 2.125 (2 1/8”)
TTA3004*C w/ TWE3004*B
29.8
N/A
0.625 (5/8”) 2.125 (2 1/8”)
Notes:
1. For line lengths other than 25', please refer to the Application Guide (SS-APG008*-EN) for charge levels, oil addition and line sizes.
2. TTA0604DA and TTA0724*A need a reducer for vapor line. (1.375 to 1.125 inch) (1 3/8” to 1 1/8”).
3. TTA2514DC and TTA3004*C are provided with a transition tube to be installed outside of the unit for front or rear access, (1.625 to
2.125 inch) (1 5/8" to 2 1/8"). See Refrigerant Charging Procedure for transition tube location and electrical connections.
IInnssttaallllaattiioonn