28
PRGD-SVX01F-EN
Troubleshooting
Use this section to assist you in diagnosing operational
problems with the purge system.
WWAARRNNIINNGG
RReeffrriiggeerraanntt uunnddeerr HHiigghh PPrreessssuurree!!
FFaaiilluurree ttoo ffoollllooww iinnssttrruuccttiioonnss bbeellooww ccoouulldd rreessuulltt iinn
aann eexxpplloossiioonn wwhhiicchh ccoouulldd rreessuulltt iinn ddeeaatthh oorr
sseerriioouuss iinnjjuurryy oorr eeqquuiippmmeenntt ddaammaaggee..
SSyysstteemm ccoonnttaaiinnss ooiill aanndd rreeffrriiggeerraanntt uunnddeerr hhiigghh
pprreessssuurree.. RReeccoovveerr rreeffrriiggeerraanntt ttoo rreelliieevvee pprreessssuurree
bbeeffoorree ooppeenniinngg tthhee ssyysstteemm.. SSeeee uunniitt nnaammeeppllaattee ffoorr
rreeffrriiggeerraanntt ttyyppee.. DDoo nnoott uussee nnoonn--aapppprroovveedd
rreeffrriiggeerraannttss,, rreeffrriiggeerraanntt ssuubbssttiittuutteess,, oorr rreeffrriiggeerraanntt
aaddddiittiivveess..
WWAARRNNIINNGG
HHaazzaarrddoouuss VVoollttaaggee!!
FFaaiilluurree ttoo ddiissccoonnnneecctt ppoowweerr bbeeffoorree sseerrvviicciinngg ccoouulldd
rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy..
DDiissccoonnnneecctt aallll eelleeccttrriicc ppoowweerr,, iinncclluuddiinngg rreemmoottee
ddiissccoonnnneeccttss bbeeffoorree sseerrvviicciinngg.. FFoollllooww pprrooppeerr
lloocckkoouutt//ttaaggoouutt pprroocceedduurreess ttoo eennssuurree tthhee ppoowweerr
ccaann nnoott bbee iinnaaddvveerrtteennttllyy eenneerrggiizzeedd.. VVeerriiffyy tthhaatt nnoo
ppoowweerr iiss pprreesseenntt wwiitthh aa vvoollttmmeetteerr..
WWAARRNNIINNGG
HHoott SSuurrffaaccee!!
FFaaiilluurree ttoo ffoollllooww iinnssttrruuccttiioonnss bbeellooww ccoouulldd rreessuulltt iinn
sseevveerree bbuurrnnss..
SSuurrffaaccee tteemmppeerraattuurreess mmaayy eexxcceeeedd 330000°°FF ((115500°°CC))..
TToo aavvooiidd ppoossssiibbllee sskkiinn bbuurrnnss,, ssttaayy cclleeaarr ooff tthheessee
ssuurrffaacceess.. IIff ppoossssiibbllee,, aallllooww ssuurrffaacceess ttoo ccooooll bbeeffoorree
sseerrvviicciinngg.. IIff sseerrvviicciinngg iiss nneecceessssaarryy wwhhiillee ssuurrffaaccee
tteemmppeerraattuurreess aarree ssttiillll eelleevvaatteedd,, yyoouu MMUUSSTT ppuutt oonn
aallll PPeerrssoonnaall PPrrootteeccttiivvee EEqquuiippmmeenntt ((PPPPEE))..
Diagnostics
The chiller controller generates diagnostics to alert the
operator to abnormal conditions. There are two kinds
of diagnostics:
• Non-latching diagnostics: Operation continues.
Alarms resolve themselves and the alarm
disappears. They are informational only.
• Latching diagnostics: Operation stops until the
condition is corrected and the diagnostic has been
manually reset from the Tracer® AdaptiView™
display or from the Tracer® TU service tool.
The following table describes the causes of diagnostics
and operating problems that can occur with purge
systems, and suggests solutions to resolving them.
Table 2. Troubleshooting a purge system
Diagnostic or Problem
Cause Solution
Purge Cprsr Suction Temp Sensor
(latching diagnostic)
Bad Sensor or LLID.
The purge refrigerant compressor suction temperature sensor has failed.
The connection has been broken or a short has occurred in the wiring, or
the LLID is not programmed or functioning correctly. Replace or repair as
required.
Purge Liquid Temp Sensor
(latching diagnostic)
Bad Sensor or LLID.
The purge liquid temp sensor has failed. The connection has been broken
or a short has occurred in the wiring, or the LLID is not programmed or
functioning correctly. Replace as required.
Purge Carbon Tank Temp Sensor
(latching diagnostic)
Bad Sensor or LLID.
The purge carbon tank temp sensor has failed. The connection has been
broken or a short has occurred in the wiring, or the LLID is not
programmed or functioning correctly. Replace as required.
Purge Liquid Level Too High (non-
latching diagnostic)
High liquid level in purge tank or
bad level switch. The level switch
was open for at least 20 minutes.
Check for restrictions in the in the vapor pick-up line and in the liquid
return line. Ensure the vapor line is sloped correctly and has no liquid
traps. Change filter drier if required. Ensure the line shutoff valves are
open.
Purge Liquid Level Too High
Continuously (latching diagnostic)
High liquid level in purge tank or
bad level switch. The level switch
was open for more than
20 minutes, or the liquid level/
refrigeration circuit restart cycle
has occurred more than four times
in 4 hours.
Check for restrictions in the in the vapor pick-up line and in the liquid
return line. Ensure the vapor line is sloped correctly and has no liquid
traps. Change filter drier if required. Ensure the line shutoff valves are
open.
Purge Carbon Regen Temp Too
Low (non-latching diagnostic)
The carbon tank temperature did
not increase more than 25°F
(-3.9°C) in the first 2 hours after
energizing the carbon tank heater.
This diagnostic is intended to identify a failed heater or sensor. Check
carbon tank heater and heater wiring. Check the carbon tank
temperature sensor and its wiring. Check the carbon tank insulation and
the surrounding ambient temperature. Check the purge unit controls and
settings.
Carbon Regeneration Temperature
Setpoint Not Satisfied (non-
latching diagnostic)
The carbon tank temperature
sensor did not reach the minimum
regeneration temperature setpoint
within 4 hours after energizing the
heater.
This is intended to identify a failing insulation system. Check carbon tank
insulation for integrity. Check ambient conditions. Check heater
operation.