Configuration
6 PTAC-SVN030B-EN
Configuration
To enter into configuration mode, press the °F/°C button
and Mode button simultaneously within 30 seconds after
energizing the wired thermostat. To advance to other
configuration modes, press the MODE button. The
following procedure describes how to configure the
model, min/max temperature, and the cooling/heating
temperatures.
1. After entering configuration mode, press either
or
to switch between either heat pump (HP) or non heat
pump (HC) models.
2. After setting the model, press MODE to set the
Mi
nimum Temperature. The LCD displays SET POINT
and MIN. Press either
or can increase/decrease
the Minimum Temperature by 1°F (1°C) increments.
3. To set the Maximum Temperature, press MODE and
the LCD displays SET POINT and MAX. Press either
or
can increase/decrease the Maximum
Temperature by 1°F (1°C) increments.
4. After setting the Minimum Tem
perature, press MODE
to set the Cooling Temperature. The LCD displays
(for cooling), ROOM, and SET POINT. Press either or
can increase/decrease the Minimum Temperature
by 1°F (1°C) increments.
5. After setting the Cooling Temper
ature, press MODE to
set the Heating Temperature. The LCD displays (for
cooling), ROOM, and SET POINT. Press either or
can increase/decrease the Minimum Temperature by
1°F (1°C
) increments.
General Information
• Once all settings are complete, the wired thermostat
commits these settings into memory.
• To reset the thermostat back to factory default, press
a
nd hold simultaneously ON/OFF and MODE for three
(3) seconds. The LCD displays all icons and the unit
returns to factory defaults noted above.