Unit Status (before Start-up)
Chiller appearance at arrival:
Pressure from TD7 (bar): ckt1: ckt2:
Phase Imbalance Rate (%):
R134a Charge (kg): ckt1: ckt2:
Circuit
1
Compressor
1A
Circuit
2
Compressor
2A
Compressor
1B
Compressor
2B
Evaporator Design Conditions
Evaporator Actual Conditions
(T):
Communications Interface Type:
Owner Witness Signature: ____________________________
Maintenance and Service
Refrigerant Field Charge Procedure
Once the system is deemed leak and moisture free, following the procedures to add refrigerant charge. Refer
to Figure 1 Unit Nameplate for refrigerant charge information.
1. Unit is empty of all refrigerant and under vacuum.
2. Attach charge hose to evaporator service valve and exclude the air in hose by refrigerant prior to open the
service valve.
3. Add charge to the evaporator according to the refrigerant type and amount indicated in the unit nameplate.
4. Close the service valve and remove the charge hose after charge.
CAUTION - Equipment Damage!
Constant water flow within allowed range through the evaporator is strictly necessary during the
whole charge process to prevent evaporator from freezing damage.
NOTICE - Equipment Damage!