Trane S9V2B060D3PSBC/D - 06 Fault Code Faulty Ground

Trane S9V2B060D3PSBC/D
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
114
S9V2-SVX001-1A-EN
DEFINITION:
Ground Fault - Incoming or chassis
ground connec!on is not sensed
Connect volt meter
to black incoming
and chassis ground
at burner box
Does meter read
~120 vac?
Disconnect incoming
electrical power to
furnace
NO
Correct earth ground.
Check opera!on
Furnace must be on a
dedicated circuit.
Check / correct all ground
connec!ons within furnace for
con!nuity. Furnace must be on a
dedicated circuit.
Disconnect incoming
electrical power to
furnace
YES
Check opera!on
06 Fault Code
Faulty Ground
TTrroouubblleesshhoooottiinngg