Unit Startup
11 2 RT-SVX24J-EN
Table 38. Service test guide for component operation — part II of II
Component
Being Tested
Component Configuration
Occ
Unocc
Relay
Sump Pump Sump Heater
Econo
Damper
Exhaust
Damper
VFD
Output
COMPRESSOR
90 - 105 Ton
1A Closed Closed 0% Default OFF OFF
1B Closed Closed 0% Default OFF OFF
2A Closed Closed 0% Default OFF OFF
2B Closed Closed 0% Default OFF OFF
120 - 162 Ton
1A Closed Closed 0% Default OFF OFF
1B Closed Closed 0% Default OFF OFF
2A Closed Closed 0% Default OFF OFF
2B Closed Closed 0% Default OFF OFF
CONDENSER FANS
90 - 105 Ton — Air Cooled
1A Closed Closed 0% Default OFF OFF
1B & 1C Closed Closed 0% Default OFF OFF
2A Closed Closed 0% Default OFF OFF
2B & 2C Closed Closed 0% Default OFF OFF
120 - 150 Ton — Air Cooled
1A Closed Closed 0% Default OFF OFF
1B Closed Closed 0% Default OFF OFF
1C & 1D Closed Closed 0% Default OFF OFF
2A Closed Closed 0% Default OFF OFF
2B & 2C Closed Closed 0% Default OFF OFF
2D Closed Closed 0% Default OFF OFF
100, 118, 128, 140, 162 Ton — Evaporative Cooled
1A Closed Closed 0% Default OFF OFF
2A Closed Closed 0% Default OFF OFF
SUPPLY FAN Closed Closed 100% Unocc OFF OFF
RETURN FAN Closed Closed 100% Default OFF OFF
EXHAUST FAN Closed Closed 100% Default OFF OFF
GAS HEAT
(Full Capacity)
Closed Closed 100% Unocc OFF OFF
Stage 1 Closed Closed 100% Unocc OFF OFF
Stage 2 Closed Closed 100% Unocc OFF OFF
Full Modulating Closed Closed 100% Unocc OFF OFF
ELECTRIC HEAT Closed Closed 100% Unocc OFF OFF
Stage 1 Closed Closed 100% Unocc OFF OFF
Stage 2 Closed Closed 100% Unocc OFF OFF
Stage 3 Closed Closed 100% Unocc OFF OFF
HYDRONIC HEAT Closed Closed 100% Default OFF OFF
OUTSIDE AIR
DAMPERS
Closed Closed 100% Default OFF OFF
EXHAUST DAMPERS Closed Closed 100% Default OFF OFF
EVAP COND
Sump Pump Closed Closed 100% Default ON OFF
Sump Heater Closed Closed 100% Default OFF ON