RT-SVX24J-EN 21
Unit Clearances
Figure 10. Minimum required clearance
(a)
(a)Unit drawing is representative only and may not accurately depict all models.
Filters
VFD
VFD
Heat
Rtn/Exh
Mtr
Rtn/Exh
VFD
Evp
F
Fltr
Sup
Mtr
Sup
VFD
Fltr
Evp
R
Heat
L&R
OptionOption
As Req.
As Req. As Req.
Std
Std StdStd
Blank Section
Final
Filter
Fnl
Fltr
As Req.
Fnl
Fltr
As Req.
Ctrl Box
L&R
Std
Outsid
Air
Outside
Exhaust
Condenser
Condenser
Exh
AH R
CBox
AH L
Cond L
Cond R
Left Side
Table 4. Minimum required clearance
Unit Option Selection (Door Swing Ft. and In.)
Standard VFD Two-side Access
Door Location Availability 90-118 120-162
Return/
Exhaust Supply Heat Reheat 90-118 120-162
Final
Filter
Energy
Recovery
Exhaust/Ret Motor Std 2' 2" 2' 2" * * * * * * *
Exhaust/Ret VFD As Req. * * 2' 2" * * * * * *
ERW Fltr
(a)
(L & R) (F) Option * * * * * * * * * 2' 2"
ERW Fltr(a) (L & R) (R) Option * * * * * * * * * 2' 2"
Filter (Front) Std 2' 8" 2' 8" * * * * * * *
Filter (Rear) Option * * * * * * 2' 2" 2' 8" *
Evap (Front) Std 2' 2" 2' 2" * * * * * * *
Evap (Rear) Std 2' 8" * * * * * * * *
or Evap (Rear) Option * * * * * 2' 2 * 2' 2" *
Supply Motor Std 2' 8" 2' 8" * * * * * * *
Supply VFD As Req. * * * 2' 2" * * * * *
Heat (Left & Right) As Req. * * * * 2' 2" * * * *
Final Filter (Front) As Req. * * * * * * * * 2' 2"
Final Filter (Rear) As Req. * * * * * * * * 2' 2"
Control Box (L & R) Std 3' 2" 3' 2" * * * * * * *
Minimum Required Clearance (Ft.)
AH_L AH_R Exh Cond_L Cond_R
Control
Box
8' 8' 8' 8' 8' 6'
(a)See Unit Dimensions for Energy Recovery Wheel location.