Unit Startup
RT-SVX24J-EN 131
Nom
Tons CFM
Outside Air Bypass
Damper Open
Outside Air Bypass
Damper Closed
Exhaust Air Bypass
Damper Open
Exhaust Air Bypass
Damper Closed
105/118
9000 0.08 0.57 0.09 0.47
12000 0.14 0.77 0.16 0.65
14000 0.19 0.93 0.21 0.78
16000 0.24 1.08 0.26 0.91
19000 0.32 1.33 0.34 1.11
21000 0.37 1.49 0.40 1.25
23000 0.44 - 0.46 -
28000 0.61 - 0.64 -
33000 0.80 - 0.82 -
38000 1.00 - 1.03 -
43000 1.23 - 1.25 -
45000 1.33 - 1.34 -
120/128
10000 0.10 0.56 0.11 0.50
12000 0.14 0.69 0.16 0.63
15000 0.20 0.89 0.23 0.85
18000 0.27 1.10 0.29 1.05
21000 0.35 1.33 0.38 1.28
24000 0.43 1.57 0.47 1.51
26000 0.50 - 0.54 -
31000 0.66 - 0.72 -
36000 0.84 - 0.91 -
41000 1.04 - 1.11 -
46000 1.26 - 1.34 -
51000 1.49 - 1.56 -
54000 1.63 - 1.71 -
130-162
13000 0.16 0.59 0.17 0.53
15000 0.20 0.69 0.22 0.63
18000 0.26 0.86 0.28 0.79
21000 0.33 1.04 0.36 0.96
23000 0.38 1.16 0.42 1.06
26000 0.45 1.36 0.50 1.24
29000 0.54 1.57 0.60 1.42
30000 0.57 - 0.63 -
35000 0.72 - 0.80 -
40000 0.89 - 0.98 -
45000 1.08 - 1.17 -
50000 1.28 - 1.38 -
55000 1.50 - 1.60 -
58000 1.63 - 1.74 -
Continued on next page