CHS-SVX02C-EN 43
Decommissioning Guidelines
Reference the following guidelines for decommissioning
rental AHUs prior to their return at the end of a rental job.
Please contact Trane Rental Services at 800-755-5115 for
any additional information.
NOTICE:
Freezing Damage!
Trane Rental AHU units are prone to freeze damage
caused by cold ambient temperatures. In addition to the
guidelines below, please refer to the Trane Rental
Services Freeze Protection Policy referenced in your
rental agreement. Failure to take the outlined
precautions may result in equipment damage for which
customer will be liable.
[ ] Turn the disconnect located on the front of the un
it to t
he
“OFF” position. Allow enough time for the supply fan to
come to a complete stop before opening any unit
access doors.
WARNING
Hazardous Voltage w/Capacitors!
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. For variable frequency drives
or other energy storing components provided by Trane
or others, refer to the appropriate manufacturer’s
literature for allowable waiting periods for discharge of
capacitors. Verify with an appropriate voltmeter that all
capacitors have discharged. Failure to disconnect
power and discharge capacitors before servicing could
result in death or serious injury.
[ ] Once the fan operation has stopped, de-energize the
mai
n power supply.
[ ] Remove all external piping, temporary manifold pieces
(see piping configuration section on p. 33), and P-trap.
Return P-trap a
nd tem
porary manifold pieces to the bin
located in the mixed air chamber that is accessed
through the filter access door.
[ ] Open all coil drains.
1. Ensure the machine is either level, or tilted toward the
water connect
ions
2. Open all drains and vents. Ensure that fluid is draining
freely. Check for d
rain line restriction if necessary.
a. Ensure drained fluid is collected and disposed of in
accordance with an
y applicable environmental
laws and regulations
3. Leave unit to drain until there
is n
o more fluid coming
out. This may take up to an hour or more. Do not
relocate or release the unit for shipment until draining
is complete.
4. Do not close the vents or valves. Leave all drains and
vents open
even after draining is complete
Recommended
5. In extreme cold conditions, flush coil with antifreeze
solution to ensure residual fluid cannot freeze. Please
contact Trane Rental Services if assistance is needed.
[ ] Remove all temporary ductwork and close manual
dampers.
[ ] Disconnect electrical cable supplied wit
h the unit from
the power supply.
[ ] Make sure all access doors are prop
erly closed.
[ ] Return additional hose, fittings, or cable (if fur
nished by
Trane Rental Services) to appropriate containers for
return shipment.
[ ] Notify Trane Rental Services (800-755-5115) if unit
needs repair or has damage.