ARTC-SVX007A-EN
13
Figure 2. Recommended chiller clearances
Rigging, Lifting, and Moving the
Chiller
The Thermafit™ TACW modular chiller can be delivered to
the customer’s site as individual modules. Limitations on
the methods and materials that can be used to rig, lift, or
move a chiller or an individual module include:
Maintain the module in an upright position at all times.
Certain configurations of modules can be top-heavy.
Move modules slowly with consideration for each
module’s center-of-gravity.
Rig, lift, and move by strapping and lifting using a
properly configured floor jack or fork lift or by overhead
means.
Position lifting beams or spreader beams to prevent
lifting straps from rubbing or contacting module side
panels or electrical boxes.
Do not use cables, chains, or any other type of
metalized strapping to lift a module.
Do not push a chiller module while directly in contact
with the floor using manual or mechanical means.
Figure 3. Recommended chiller rigging assembled
unit
Chiller Placement
The chiller must be positioned on a firm level surface using
waffle rubber isolation pads.
Installation Mechanical