ARTC-SVX007A-EN
13
Figure 2. Recommended chiller clearances
Rigging, Lifting, and Moving the
Chiller
The Thermafit™ TACW modular chiller can be delivered to
the customer’s site as individual modules. Limitations on
the methods and materials that can be used to rig, lift, or
move a chiller or an individual module include:
• Maintain the module in an upright position at all times.
• Certain configurations of modules can be top-heavy.
Move modules slowly with consideration for each
module’s center-of-gravity.
• Rig, lift, and move by strapping and lifting using a
properly configured floor jack or fork lift or by overhead
means.
• Position lifting beams or spreader beams to prevent
lifting straps from rubbing or contacting module side
panels or electrical boxes.
• Do not use cables, chains, or any other type of
metalized strapping to lift a module.
• Do not push a chiller module while directly in contact
with the floor using manual or mechanical means.
Figure 3. Recommended chiller rigging assembled
unit
Chiller Placement
The chiller must be positioned on a firm level surface using
waffle rubber isolation pads.
Installation Mechanical