60
ARTC-SVX007A-EN
1. The fault is reset, and the compressor is made
available for normal use again by switching into the idle
state.
2. After overheating faults (motor or electronics have
become too hot), the compressor is given some extra
time to cool down by changing into the timeout state.
This ensures that the compressor cools down well
below its alarm threshold before it can be started again.
3. Some faults cannot be reset by the controller, for
example when the compressor is damaged. The
controller then takes this compressor out of circulation
by switching into the offline state.
Timeout State
The compressor has recovered from an overheat fault. It is
given some additional time to cool down before it becomes
available.
Sequence of Operations