ARTC-SVX007A-EN
47
Table 13. BMS listing - BO (continued)
Tag Name Array
Array
Offset
Object
Type
Object
Instance
Modbus
Address
Chiller: Condenser Flow Fault with DPS Chiller Faults 4 BO 219 10205
Chiller: Evaporator Flow Switch
Chiller Faults 5 BO 220 10206
Chiller: Condenser Flow Switch Chiller Faults 6 BO 221 10207
Chiller: Evaporator Pump Enable
Chiller Faults 7 BO 222 10208
Chiller: Condenser Pump Enable
Chiller Faults 8 BO 223 10209
Chiller: Low Lift Active Circuit 1 Chiller Faults 9 BO 224 10210
Chiller: Low Lift Active Circuit 2 Chiller Faults 10 BO 225 10211
Chiller: Low Lift Active Circuit 3 Chiller Faults 11 BO 226 10212
Chiller: Low Lift Active Circuit 4 Chiller Faults 12 BO 227 10213
Chiller: Barrel Isolation Circuit 1 Chiller Faults 13 BO 228 10214
Chiller: Barrel Isolation Circuit 2 Chiller Faults 14 BO 229 10215
Chiller: Evaporator Pump1 Fault
Chiller Faults 16 BO 230 10217
Chiller: Evaporator Pump1 Flow Alarm
Chiller Faults 17 BO 231 10218
Chiller: Evaporator Pump2 Fault
Chiller Faults 18 BO 232 10219
Chiller: Evaporator Pump2 Flow Alarm
Chiller Faults 19 BO 233 10220
Chiller: Condenser Pump1 Fault
Chiller Faults 20 BO 234 10221
Chiller: Condenser Pump1 Flow Alarm
Chiller Faults 21 BO 235 10222
Chiller: Condenser Pump2 Fault
Chiller Faults 22 BO 236 10223
Chiller: Condenser Pump2 Flow Alarm
Chiller Faults 23 BO 237 10224
Chiller: At Maximum Capacity
Chiller Faults 24 BO 238 10225
Chiller: No Compressor Available Fault
Chiller Faults 25 BO 239 10226
Note: Chiller control system provides data for up to 6
compressors.
The BMS Listing has the following characteristics:
• All values are integers.
• Some of the values like temperatures and pressures
have an implied decimal place; this means that a value
of 450 read from the chiller via BMS interface for Chiller
Outlet Temperature, CHIL_OUT_04, means 45.0 °F (in
imperial configuration).
• Some values are enumerated integers:
– Chiller State:
Figure 32. Chiller state map
– Compressor State:
Figure 33. Compressor state map
Table 14. Fan state map
Fan State Definition
Value Label
0 Off
1 Hand
2 Ready
3 FreeCool
Operating Procedures