Table 21. Chiller / Compressor alarms / Faults listing (continued)
Code
Description
Reset
(a)
Period
(b)
Start-up
(c)
Steady
(d)
Active
in Off
(e)
Alarm
Relay
(f)
Warning
Relay
(g)
Compressors
(h)
a4N TC4 ANC - SCR Temperature -1 0 0 0 X X -
a4O TC4 ANC - Super Heat -1 0 0 0 X X -
A92 Evaporator low flow rate alarm 5 60 5 5 X INTERLOCK
A94 Condenser low flow rate alarm 5 60 5 5 X -
A95 Master connection lost -1 0 15 0 X -
N01 Network Error -1 90 60 60 X -
N02 Master Error -1 90 60 60 X -
N03 Alarm Node 1 -1 90 60 0 X X -
N04 Alarm Node 2 -1 90 60 0 X X -
N05 Alarm Node 3 -1 90 60 0 X X -
N06 Alarm Node 4 -1 90 60 0 X X -
A01 General alarm -1 60 5 1 X X -
S01 Ambient Temp Sensor Fault -1 60 5 5 X X -
S02 Free Cool LW Temp Sensor Fault -1 60 5 5 X X -
S03 Evap DP Sensor Fault -1 60 5 5 X X -
S04 Cond DP Sensor Fault -1 60 5 5 X X -
PF1 Chiller Pump 1 Fault -1 60 5 1 X X -
PF3 Condenser Pump 1 Fault -1 60 5 1 X X -
PA1 Chiller Pump 1 Flow Alarm -1 60 5 5 X X -
PA3 Condenser Pump 1 Flow Alarm -1 60 5 5 X X -
PF2 Chiller Pump 2 Fault -1 60 5 1 X X -
PF4 Condenser Pump 2 Fault -1 60 5 1 X X -
PA2 Chiller Pump 2 Flow Alarm -1 60 5 5 X X -
PA4 Condenser Pump 2 Flow Alarm -1 60 5 5 X X -
TF1 Cooling Tower Fault -1 60 5 1 X X -
S05 Wet Bulb Temp Sensor Fault -1 60 5 5 X X -
(a)
Reset type of the alarm / fault reset:
“– 1”. Automatic when the alarm occurs the reset is done automatically if the alarm conditions no longer persist.
“0”. Manual when the alarm occurs, the reset has to be done compulsorily by the user (maintainer or service) by pressing a key combination on the user interface.
“>0”. Semiautomatic alarm is automatically reset for the "Reset" number of attempts in the specified "Period" of time, but if the alarms occur one more time, it becomes
Manual.
(b)
Period is the period of time where the alarm can occur for "Reset" number of times (minutes) with the automatic reset and without becoming manual.
(c)
Startup is the delay (second) in the alarm during the startup phase.
(d)
Steady is the delay (second) in the alarm during the steady phase.
(e)
Active in Off if this box is checked the alarm will be enabled even if the machine is in OFF condition.
(f)
Alarm Relay if this box is checked, when the alarm occurs the corresponding digital output (configured in the “Digital Output” tab as "Alarm") will be activated.
(g)
Warning Relay if this box is checked, when the alarm occurs the corresponding digital output (configured in the “Digital Output” tab as "Warning") will be activated.
(h)
Compressors with this column there is the possibility to stop/run for security reasons the compressors when the alarm occurs. There are two options:
OFF when alarm / fault occurs compressors stop.
INTERLOCK when alarm / fault occurs compressors lock out.
Note: For a complete list of compressor, motor and bearing
faults:https://files.danfoss.com/download/Drives/
Service%20Manual%20(M-SV-001-EN%20Rev.%
20E).pdf