102
Factory Settings
Special Default Parameter Settings
Some applications of the TR1 Series VFDs have differences in factory
set default parameters. The table below lists default settings that differ by
application model identification. Motor data, parameters 102 through
106, are factory set for each of the application models listed.
NOTE
Choosing Initialization in parameter 620,
Operating Mode, resets drive to standard default
parameters. Any special application
programming performed at the factory, during
start-up or thereafter, will be lost. As a backup,
upload drive settings into the driveís local
control panel (LCP) keypad as described in
parameter 004, LCP Copy.
Special Default Param eter Settings
In te lliP a k a n d V o y ager III
Parameter Title Setting
007 Large Display Readout Frequency (Hz)
012 Hand Start Button Disabled
101 Torque Characteristics Multiple Motors
108 Start Voltage with Multiple Motors 0.0 V
114 DC Braking Current 0%
201 O utput Frequency, Low Limit IntelliP a k = 2 2 H z
Voyager III = 35 Hz
2 0 4 M in im u m R e fe re n ce In te lliP a k = 2 2 H z
Voyager III = 35 Hz
206 Ram p Up Time 30 sec.
207 Ram p Down Time 30 sec.
215 Current Lim it Set Equal to Parameter 105
304 Term inal 27, D igital Input C oast Stop, Inverse
308 Analog Input Reference Reference
314 Term inal 60, Analog Input Current No Operation
400 Reset Function Autom atic Reset x 3
402 Flying Start Enabled
407 Switching Frequency 8.0 kHz (except for 40 hp,
208/230 V set at 4.5 kHz and all
575 V are 7.0 kHz)
410 Function at Input Phase Loss Autoderate and W arning
411 Function at Drive Over Temperature Autoderate and W arning
412 Trip Delay at O vercurrent OFF
M -Series and T-Series Climate Changer
P a ra m e te r T itle S e ttin g
201 O utput Frequency, Low Limit 20 Hz
204 Minimum Reference 20 Hz
206 Ramp Up Time 30 sec.
207 Ramp Down Time 30 sec.
215 Current Lim it 1.1 x Drive Rated Current
304 Term inal 27, Digital Input Coast Stop, Inverse
308 Term inal 53, Analog Input Reference
402 Flying Start Enabled
407 Sw itching Frequency Set to m ax for hp rating
C o m m e rc ia l S e lf C o n ta in e d
P a ra m e te r T itle S e ttin g
201 O utput Frequency, Low Limit 22 Hz
204 Minimum Reference 22 Hz
206 Ramp Up Time 30 sec.
207 Ramp Down Time 30 sec.
304 Term inal 27, Digital Input Coast Stop, Inverse
308 Term inal 53, Analog Input Reference
314 Analog Input Current No O peration
4 0 1 A u to m a tic R e s et T im e 3 s e c.
402 Flying Start Enabled
407 Sw itching Frequency Set to m ax for hp rating
410 M ains Imbalance Autoderate and W arning
411 Function at Drive Over Temperature Autoderate and W arning
Packaged Clim ate C hanger
P a ra m e te r T itle S e ttin g
201 O utput Frequency, Low Limit 22 Hz
206 Ramp Up Time 30 sec.
207 Ramp Down Time 30 sec.
304 Term inal 27, Digital Input Coast Stop, Inverse
308 Term inal 53, Analog Input Reference
326 Relay 2, Output Function No Alarm
407 Sw itching Frequency Set to m ax for hp rating