Relay Card Functions
Parameters 700 through 711
Parameters 700 through 711 are only activated if a relayoption card is
installed in the drive. A relay card can be field installed in the drive if
desired.
Activation/deactivation can be programmed in parameters 701, 704,
707 and 710, Relay 6, 7, 8 and 9, ON Delay; and parameters 702,
705, 708 and 711 Relay 6, 7, 8 and 9, OFF Delay.
700 Relay 6, Function (RELAY6 FUNCTION)
703 Relay 7, Function (RELAY7 FUNCTION)
706 Relay 8, Function (RELAY8 FUNCTION)
709 Relay 9, Function (RELAY9 FUNCTION)
Function:
This output activates a relay.
Relay outputs 6, 7, 8 and 9 can be used for showing status and
warnings. The relay is activated when the conditions for the relevant
data values have been fulfilled. Because these have the same possible
functions as relay 1, see the description under parameter 323.
701 Relay 6, ON Delay (RELAY6 ON DELAY)
704 Relay 7, ON Delay (RELAY7 ON DELAY)
707 Relay 8, ON Delay (RELAY8 ON DELAY)
710 Relay 9, ON Delay (RELAY9 ON DELAY)
Value:
0 to 600 sec. 0 sec.
Function:
This parameter allows a delay of the activation of relays 6, 7, 8 and 9
(terminals 1, and 2).
Description of choice:
Enter the desired value.
702 Relay 6, OFF Delay (RELAY6 OFF DELAY)
705 Relay 7, OFF Delay (RELAY7 OFF DELAY)
708 Relay 8, OFF Delay (RELAY8 OFF DELAY)
711 Relay 9, OFF Delay (RELAY9 OFF DELAY)
Value:
0 to 600 sec. 0 sec.
Function:
This parameter is used to delay the deactivation time of relays 6, 7, 8
and 9 (terminals 1 and 2).
Description of choice:
Enter the desired value.
This parameter allows a delay of the activation of relays 6, 7, 8 and 9
(terminals 1, and 2).
Electrical Installation of the Relay Card
The relays are connected as shown below.
To achieve double isolation, mount the plastic foil as shown below.
Relay 6-9
A-B make, A-C break
Max. 240 VAC, 2 Amp