Relay outputs Relay Number: 1 2
Parameter: 323 326
Value:
No function (NO FUNCTION) [0] [0]
Drive ready (READY) [1] [1]
Waiting for start (ENABLED & NO WARNING) [2] [2]
Running (RUNNING) [3] ★ [3]
Running at reference value (RUNNING AT REFERENCE) [4] [4]
Running, no warning (RUNNING NO WARNING) [5] [5]
Local reference active (DRIVE IN LOCAL REF) [6] [6]
Remote controlled references active (DRIVE IN REMOTE REF.) [7] [7]
Alarm (ALARM) [8] [8]
Alarm or warning (ALARM OR WARNING) [9] [9]
No alarm (NO ALARM) ★ [10] [10]
Current limit (CURRENT LIMIT) [11] [11]
Safety interlock (SAFETY INTERLOCK) [12] [12]
Start command active (START SIGNAL APPLIED) [13] [13]
Running in reverse (RUNNING IN REVERSE) [14] [14]
Thermal warning (THERMAL WARNING) [15] [15]
Hand mode active (DRIVE IN HAND MODE) [16] [16]
Auto mode active (DRIVE IN AUTO MODE) [17] [17]
Sleep mode active (SLEEP MODE) [18] [18]
Output frequency lower than low frequency, parameter 223 (F OUT < F LOW) [19] [19]
Output frequency higher than high frequency, parameter 224 (F OUT > F HIGH) [20] [20]
Out of frequency range (FREQ RANGE WARN.) [21] [21]
Output current lower than low current, parameter 221 (I OUT < I LOW) [22] [22]
Output current higher than high current, parameter 222 (I OUT > I HIGH) [23] [23]
Out of current range (CURRENT RANGE WARN.) [24] [24]
Out of feedback range (FEEDBACK RANGE WARN.) [25] [25]
Out of reference range (REFERENCE RANGE WARN.) [26] [26]
Relay 123 (RELAY 123) [27] [27]
Input phase loss (MAINS PHASE LOSS) [28] [28]
Control word bit 11/12 (CONTROL WORD 11/12) [29] [29]
Relay Outputs
Relay 1:
Relay 2:
4 - 5 normally open
Maximum: 30 VAC, 1 A,
42.5 VDC, 1 A
The low voltage relay terminals are
located on the control wiring terminal
strips.
Function:
Relay outputs 1 and 2 can be used to give the present status or a
warning. See the description of options in Analog/Digital Outputs.
Control word bit 11/12 [29]. Relay 1 and relay 2 can be activated
through serial communication. Bit 11 activates relay 1 and bit 12
activates relay 2.
1 - 3 normally closed, 1 - 2 normally open
Maximum: 240 VAC/DC, 2 A
Minimum: 24 VAC, 100 mA;
24 VDC, 10 mA
The high voltage relay connections are located
near the input power and motor terminals.
If parameter 556, Bus Time Interval Function, becomes active, relay 1
and relay 2 will cut out if they are activated through serial
communication.
Description of choice:
Select the output relay function.
Relay 02