36
011 Unit of Local Reference (UNIT OF LOC REF)
Value:
Hz (HZ) [0]
★ % of output frequency range (%) (% OF FMAX) [1]
Function:
This parameter sets the unit that will be displayed in Display Mode IV
when the drives speed is being controlled locally.
Description of choice:
Choose the desired unit for local reference.
012 Hand Start on LCP (HAND START BUTTON)
Value:
Disable (DISABLE) [0]
★ Enable (ENABLE) [1]
Function:
This parameter allows disabling the Hand/Start key on the keypad.
Description of choice:
If Disable is selected in this parameter, the Hand/Start key will be
disabled.
013 OFF/STOP on LCP (STOP BUTTON)
Value:
Disable (DISABLE) [0]
★ Enable (ENABLE) [1]
Function:
This parameter allows disabling the Off/Stop key on the keypad.
Description of choice:
If Disable is selected in this parameter, the Off/Stop key will be disabled.
CAUTION
!
OFF/STOP Key Disabled!
If Disable is selected in parameter 013, the motor
cannot be stopped by pressing the OFF/STOP
key on the keypad. Use of the Disable option
could result in injury or equiment or property
damage.
008 Small Readout 1
(SMALL READOUT 1)
Value:
✭ Reference, % [1]
Function:
This parameter selects the meter shown on the left display on line 1.
Showing three different meters on line 1 is recommended when setting
up the PID. This allows tracking how the process reacts to a change of
reference.
Description of choice:
See parameter 007, Large Readout, for values that may be selected.
009 Small Readout 2
(SMALL READOUT 2)
Value:
★ Motor current [A] [5]
Function:
This parameter selects the meter shown on the center display on line 1.
Showing three different meters on line 1 is recommended when setting
up the PID.
Description of choice:
See parameter 007, Large Readout, for values that may be selected.
010 Small Readout 3
(SMALL READOUT 3)
Value:
★ Power [HP] [7]
Function:
This parameter selects the meter shown on the right display on line 1.
Showing three different meters on line 1 is recommended when setting
up the PID.
Description of choice:
See parameter 007, Large Readout, for values that may be selected.
✭ I