DISPLAY
WORD
DESRIPTION
RUN REQ.
Unintended Start!
When in Run Request mode, motor may restart at any time without warning.
The drive, motor, and any driven equipment must be in operational readiness.
Failure to be in operational readiness could result in death, serious injury, or
equipment and property damage.
A start command has been given, but the motor will not be started until a
Run Permission signal is received via a digital input.
JOG Jog has been enabled via a digital input or via serial communication.
JOG REQ.
Unintended Start!
When in Jog Request mode, motor may restart at any time without warning.
The drive, motor, and any driven equipment must be in operational readiness.
Failure to be in operational readiness could result in death, serious injury, or
equipment and property damage.
A start command has been given, but the motor will rem ain stopped until a
Run Permission signal is received via a digital input.
FRZ.OUT The output frequency has been frozen.
FRZ.REQ
Unintended Start!
When in Freeze Request mode, motor may restart at any time without
warning. The drive, motor, and any driven equipment must be in operational
readiness. Failure to be in operational readiness could result in death, serious
injury, or equipment and property damage.
A start command has been given, but the motor will rem ain stopped until a
Run Permission signal is received via a digital input.
START F/R Reversing and start on terminal 19, parameter 303, Digital Inputs, and Start
on terminal 18, parameter 302, Digital Inputs, are enabled at the same time.
The m otor will rem ain stopped until one of the signals becomes a logic ‘0.’
AMA RUN Automatic motor adaptation has been enabled in parameter 107, Automatic
Motor Adaptation, AMA.
AMA STOP Automatic motor adaptation has been completed. The drive is now ready for
operation after the Reset signal has been given. Note that the motor will start
after the drive has received the Reset signal.
STANDBY The drive is able to start the motor when a start command is received.
STOP The motor has been stopped via a stop signal from serial communication.
DC STOP The DC brake has been enabled in parameters 114 through 116.
UN.READY The drive is ready for operation, but terminal 27 is a logic ‘0’ and/or a
Coasting Command has been received via the serial communication.
NOT READY The drive is not ready for operation, because of a trip or because OFF1,
OFF2 or OFF3 is a logic ‘0.
START IN. This status will only be displayed if, in param eter 599, Profidrive [1] has been
selected and OFF2 or OFF3 is a logic 0.’
XXXX The microprocessor of the control has stopped and the drive is not
operating. The cause may be noise on the power line, motor leads or control
wires.
WARNING
!
WARNING
!
WARNING
!