Digital input
function
Description
[64] Counter B (down) Input for decrement counting in the SLC
counter.
[65] Reset Counter B Input for reset of counter B.
[101] Sleep A signal applied puts the frequency
converter into sleep mode.
Table 3.3 Digital Input Functions
Selected
preset
reference:
Preset
reference bit 2
Preset
reference bit 1
Preset
reference bit 0
Preset
reference 0
000
Preset
reference 1
001
Preset
reference 2
010
Preset
reference 3
011
Preset
reference 4
100
Preset
reference 5
101
Preset
reference 6
110
Preset
reference 7
111
Table 3.4 Selected Preset Reference
5-10 Terminal 18 Digital Input
Parameter for conguring the input function on input terminal
18. Refer to Table 3.3 for setting options.
Option: Function:
[0] No operation
[1] Reset
[2] Coast inverse
[3] Coast and reset inverse
[4] Quick stop inverse
[5] DC-brake inverse
[6] Stop inverse
[7] External Interlock
[8]
*
Start
[9] Latched start
[10] Reversing
[11] Start reversing
[14] Jog
[16] Preset ref bit 0
[17] Preset ref bit 1
[18] Preset ref bit 2
[19] Freeze reference
[20] Freeze output
5-10 Terminal 18 Digital Input
Parameter for conguring the input function on input terminal
18. Refer to Table 3.3 for setting options.
Option: Function:
[21] Speed up
[22] Speed down
[23] Set-up select bit 0
[34] Ramp bit 0
[37] Fire Mode
[52] Run permissive
[53] Hand start
[54] Auto start
[60] Counter A (up)
[61] Counter A (down)
[62] Reset Counter A
[63] Counter B (up)
[64] Counter B (down)
[65] Reset Counter B
[101] Sleep
5-11 Terminal 19 Digital Input
Parameter for conguring the input function on input terminal
19.
Option: Function:
[0]
*
No operation
[1] Reset
[2] Coast inverse
[3] Coast and reset inverse
[4] Quick stop inverse
[5] DC-brake inverse
[6] Stop inverse
[7] External Interlock
[8] Start
[9] Latched start
[10] Reversing
[11] Start reversing
[14] Jog
[16] Preset ref bit 0
[17] Preset ref bit 1
[18] Preset ref bit 2
[19] Freeze reference
[20] Freeze output
[21] Speed up
[22] Speed down
[23] Set-up select bit 0
[34] Ramp bit 0
[37] Fire Mode
[52] Run permissive
[53] Hand start
[54] Auto start
[60] Counter A (up)
[61] Counter A (down)
[62] Reset Counter A
[63] Counter B (up)
Parameters Programming Guide
BAS-SVP16B-EN 02/2017 All rights reserved. 49
3