5-11 Terminal 19 Digital Input
Parameter for conguring the input function on input terminal
19.
Option: Function:
[64] Counter B (down)
[65] Reset Counter B
[101] Sleep
5-12 Terminal 27 Digital Input
Parameter for conguring the input function on input terminal
27. When parameter 0-03 Regional Settings is set to [0] Interna-
tional, the default value is [2] Coast inverse. When
parameter 0-03 Regional Settings is set to [1] North America, the
default value is [7] External Interlock.
Option: Function:
[0] No operation
[1] Reset
[2] Coast inverse
[3] Coast and reset inverse
[4] Quick stop inverse
[5] DC-brake inverse
[6] Stop inverse
[7] External Interlock
[8] Start
[9] Latched start
[10] Reversing
[11] Start reversing
[14] Jog
[16] Preset ref bit 0
[17] Preset ref bit 1
[18] Preset ref bit 2
[19] Freeze reference
[20] Freeze output
[21] Speed up
[22] Speed down
[23] Set-up select bit 0
[34] Ramp bit 0
[37] Fire Mode
[52] Run permissive
[53] Hand start
[54] Auto start
[60] Counter A (up)
[61] Counter A (down)
[62] Reset Counter A
[63] Counter B (up)
[64] Counter B (down)
[65] Reset Counter B
[101] Sleep
5-13 Terminal 29 Digital Input
Parameter for conguring the input function on input terminal
29.
Option: Function:
[0] No operation
[1] Reset
5-13 Terminal 29 Digital Input
Parameter for conguring the input function on input terminal
29.
Option: Function:
[2] Coast inverse
[3] Coast and reset inverse
[4] Quick stop inverse
[5] DC-brake inverse
[6] Stop inverse
[7] External Interlock
[8] Start
[9] Latched start
[10] Reversing
[11] Start reversing
[14]
*
Jog
[16] Preset ref bit 0
[17] Preset ref bit 1
[18] Preset ref bit 2
[19] Freeze reference
[20] Freeze output
[21] Speed up
[22] Speed down
[23] Set-up select bit 0
[32] Pulse input
[34] Ramp bit 0
[37] Fire Mode
[52] Run permissive
[53] Hand start
[54] Auto start
[60] Counter A (up)
[61] Counter A (down)
[62] Reset Counter A
[63] Counter B (up)
[64] Counter B (down)
[65] Reset Counter B
[101] Sleep
5-34 On Delay, Digital Output
Range: Function:
0.01 s
*
[0 - 600 s] Enter the delay time before the digital
output is switched on. The digital output
(terminal 42/45) condition must not be
interrupted during the delay time.
5-35 O Delay, Digital Output
Range: Function:
0.01 s
*
[0 - 600 s] Enter the delay time before the digital
output is switched o. The digital output
(terminal 42/45) condition must not be
interrupted during the delay time.
Parameters TR150 and TR170
50 02/2017 All rights reserved. BAS-SVP16B-EN