BAS-SVU025A-EN 11
Product Overview
Licensing and Hardware
The number of devices that are supported is limited by the number within the application license.
The maximum amount is 240 devices in a single license. As ofTracer SC version 3.0, allTracer SCs
ship with a base license installed.The order number for an SC Application license is
BMCF000AAA0AE00 (15 devices).
To utilize the expanded communications functionality for multi-SC facilities, the following are
required:
OneTracer SC with an Application license
One or moreTracer SCs with a Base license
Setup Requirements
The following are required for setup and normal operation:
Scenario 1: Single SC Facility
Tracer SC must have an application license in order to install equipment and facilitate control.
Ethernet port 1 must be used for communication over BACnet/IP.
BACnet MS/TP port network number cannot exceed 4193.
Scenario 2: Multi-SC Facility
OneTracer SC must have an application license in order to install equipment and facilitate
control.
AdditionalTracer SCs do not require a license.
Ethernet port 1 must be used for communication between multiple SCs over BACnet/IP
Tracer SC Device IDs must be unique.
BACnet MS/TP port network number cannot exceed 4193.
Tracer SCs on separate subnets must have one BBMD per subnet.
UDP ports must be the same across all SCs in the facility.
Note: Both theTracer SC-App and theTracer SC-Base must be configured to communicate to each
other over BACnet/IP.They can reside on the same network subnet or on a separate subnet.
Scenario 3: Trane Intelligent Services (TIS)
No additional license required;Tracer SC isTIS-Ready out of the box.
ConfigureTracer SC Ethernet port 1 or 2 to communicate to the Internet.
TIS must be enabled.
For more information about Trane Intelligent Services, see TIS Technical Specifications”,
SRV-PRC011-EN.
License Type TIS Ready Multi SC Ready BAS App
Base Up to 5 devices Yes N/A
Application Up to 120 devices Yes Up to 240 devices