Introduction for TD-5 Installation Guide
RT-SVX49C-EN 7
Specifications and Agency
Compliance
Specification
Input power:
24 VAC ± 15%, 21 VA, 50/60Hz; 24VDC +/-
10%, 400mA.
Storage
temperature
:
–67°F to 203°F (–55°C to 95°C)
Humidity: Between 5% to 100% (non-
condensi
ng)
Operating
temperature
:
Temperature: –40°F to 158°F (–40°C to 70°C)
Humidity: Between 5% to 100% (non-
condensi
ng)
Mounting weight:
Mounting surface must support 0.93 lb (422
gr
ams)
Mounting Type: VE
SA (75 mm x 75 mm)
Environmental
rating
(enclos
ure):
IP55 (dust and strong water protection)
(PN: X19070632020)
Display color
TFT LCD, 800 nits brightness, 16-bit color
Agency Compliance
• UL916 PAZX, Open Energy Management Equipment
• UL94-5V, Flammability
• FCC CFR Title 47, Part 15.109: Class A Limit, (30 MHz – 4 GHz)
• CE EMC Directive 2004/108/EC
Supported Languages
The TD-5 display supports 26 built-in languages. For help
on how to select a specific language for the display, see
“Language,” p. 36.
Arabic Greek Portuguese (Brazil)
Chinese (Simplified) Hebrew Portuguese (Portugal)
Chinese (Traditional) Hungarian Romanian
Czech Indonesian Russian
Dutch Italian Spanish (Mexico)
English Japanese Spanish (Spain)
French Korean Swedish
French Canadian Norwegian Thai
German Polish