Table 67. Local and remote heat with local priority and no fan present
Configuration Method of control
Local Remote Stage 1 Stage 2 Stage 3
PWM electric
(1 to 2 stages)
priority
On/Off electric
(1 stage)
Local PI capacity loop
Local heat capacity = 1/2 or 2/3 of total capacity
Local heat controls total capacity from 0% to 50% or 0% to 67%
PWM Output
R
emote capacity
Remote heat capacity = 1/2 or
1/3 of to
tal capacit
y
On: total capacity 10
0%
Off: t
otal capacity 50% (or
67%
)
Total capacity is limited by communicated auxiliary heat enable.
On/Off electric
(1 to 2 stages)
priority
On/Off electric
(1 stage)
Local thermostatic
On: Zt < HSP
Off: Zt HSP + 0.5°F
L
ocal thermostatic
On: Zt < HSP – 1°F
Off: Zt HSP – 0.5°F
Remote thermostatic
On: Zt < HSP – 2°F
Off: Zt HSP – 1.5°F
Each stage represents an equal percentage of total capac
ity. Total capacity is limited by
communicated auxiliary heat enable.
On/Off hot water
(1 stage) priority
On/Off hot water
(1 stage)
Local thermostatic
On: Zt < HSP
Off: Zt HSP + 0.5°F
R
emote thermostatic
On: Zt < HSP – 1°F
Off: Zt HSP – 0.5°F
Not applicable
Each stage represents an equal percentage of total capacity.
To
tal capacity is limited by communicated auxiliary heat enable.
Not applicable
On/Off hot water
(1 stage) priority
Modulating hot
wat
er
Local capacity or thermostatic
Local On/Off valve capacity =
1/2 tot
al capacit
y
On: total capacity > 50% or Zt
< HSP – 0.5°F
Off:
total capacity 0 %
o r Z t
HSP + 0.5°F
Remote PI capacity loop
Remote modulating calve capacity = 1/2 total capacity
Remote valve controls total capacity from 51% to 100%
Valve drive incrementally open/closed
Total capacity is limited by communicated auxiliary heat enable.
Modulating hot
wa
t
er
priority
On/Off hot water
(1 stage)
Local PI capacity loop
Local modulating valve capacity = 1/2 total capacity
Local valve controls total capacity from 0% to 50%
Valve drive incrementally open/closed
Remote capacity
Remote On/Off valve capacity
= 1/2 total c
apaci
ty
On: total capacity > 100%
Off: total capacity 50%
Total capacity is limited by communicated auxiliary heat enable.
CNT-SVX17G-EN 103
Appendix D: Reheat Actuation Schedule Tables
Note: This remote stage is On, Zt < HSP – 1°F / Off, Zt HSP – 0.5°F if only one stage of local heat is present.
Abbreviations: Zt = Zone temperature; HSP = Heating setpoint
Table 68. Local and remote heat with remote priority and no fan present
Configuration Method of control
Local Remote Stage 1 Stage 2 Stage 3
PWM electric
(1 to 2 stages)
On/Off electric
(1 stage) priority
Remote capacity or
thermos
tatic
R
emote heat capacity = 1/2 or
1/3 of total capaci
ty
On: total capacity 50%
(o
r
33%) or Zt < HSP – 0.5°F
Off: total capacity 0 %
o r Z t
HSP + 0.5°F
Local PI capacity loop
Local heat capacity = 1/2 or 2/3 of total capacity
Local heat controls total capacity from 51% to 100% or 34% to
100% PWM Out
put
Total capacity is limited by communicated auxiliary heat enable.
On/Off electric
(1 to 2 stages)
On/Off electric
(1 stage) priority
Remote thermostatic
On: Zt < HSP
Off: Zt HSP +
0.5°F
L
ocal thermostatic
On: Zt < HSP – 1°F
Off: Zt HSP
– 0.5°F
Local thermostatic
On: Zt < HSP – 2°F
Off: Zt HSP
– 1.5°F
Each stage represents an equal percentage of total capac
ity. Total capacity is limited by
communicated auxiliary heat enable.