94 CNT-SVX17G-EN
Appendix C: Mode Control Operation
Morning warm-
up
Don’t care Morning warm-up
Unoccupied
Occupied
Bypass
Standby
Air valve
Reheat
Fan
Vent req
Enabled
Enabled
Enabled
Disabled
STC
Morning warm-up
Cool Don’t care Cool Unoccupied
Air valve
Reheat
Fan
Vent req
Enabled
Enabled
Enabled
Disabled
STC
Unoccupied cooling
Occupied
Bypass
Standby
Air valve
Reheat
Fan
Vent req
Enabled
Enabled
Enabled
Enabled
STC
Occupied cooling
Night purge Don’t care Night purge
Unoccupied
Occupied
Bypass
Standby
Air valve
Reheat
Series fan
Parallel fan
Vent req
Enabled
Disabled
Enabled
Disabled
Disabled
STC
Pre-cool
Pre-cool Don’t care Pre-cool
Unoccupied
Occupied
Bypass
Standby
Air valve
Reheat
Series fan
Parallel fan
Vent req
Enabled
Disabled
Enabled
Disabled
Disabled
STC
Pre-cool
Off Don’t care Off
Unoccupied
Occupied
Bypass
Standby
Air valve
Reheat
Fan
Vent req
Disabled
Disabled
Disabled
Disabled
Off
Maximum heat Don’t care Maximum heat
Unoccupied
Occupied
Bypass
Standby
Air valve
Reheat
Fan
Vent req
Enabled
Enabled
Enabled
Disabled
STC
Maximum heat
Calibrate Don’t care Calibrate
Unoccupied
Occupied
Bypass
Standby
Air valve
Reheat
Fan
Vent req
Enabled
Disabled
Enabled
Disabled
Calibrate
a.nvoHeatCool/reported unit status mode determined by the controller.
Controller state Sub state
nvoHeat
Cool
Reported
unit
status.
mode
Manual output test
Step 1
throu
gh 8
Tes t Te st
Flow override (via nvi or */**)
f
Tes t Te st
Water valve override Tes t Te st
Auto-commissioning Tes t Te st
Stand-alone air balancing Tes t Te st
Calibration Calibrate Calibrate
STC: construction Heat Heat
STC: space temperature fails Cool Cool
Emergency override Don’t care
e
Don’t
care
e
Unit shutdown Off Off
Off Off Off
Table 62. Space temperature control VAV unit operation (continued)
nvi Applic
Mode
nvi Heat Cool
nvoHeatCool
a, c
nvoUnitStatus.
mode
nvoEffect
Occup
Output
b
Operation
Temp control
sequence

Table of Contents

Other manuals for Trane Tracer VV550

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Tracer VV550 and is the answer not in the manual?

Trane Tracer VV550 Specifications

General IconGeneral
BrandTrane
ModelTracer VV550
CategoryController
LanguageEnglish

Related product manuals