Appendix D: Reheat Actuation Schedule Tables
0.5 to 33
Enabled: Limited
by communicated
auxiliary heat
enable
Disabled Disabled
0 or
C
ommunicated
auxiliary heat
enable value
0 Disabled Disabled Disabled 0
On/Off
elec
tric
(1 to 3
stages)
None 1
0.5 to
10
0
Enabled. On/Off Not applicable Not applicable 0 or 100
0 Disabled Not applicable Not applicable 0
2 50 to 100 Enabled. On/Off Enabled. On/Off Not applicable 0, 50, or 100
0.5 to
49
.5
Enabled. On/Off Disabled Not applicable 0 or 50
0 Disabled Disabled Not applicable 0
3
67.5 to
10
0
Enabled. On/Off Enabled. On/Off Enabled. On/Off 0, 33, 67, or 100
34 to 67 Enabled. On/Off Enabled. On/Off Disabled 0, 33, or 67
0.5 to
33
.5
Enabled. On/Off Disabled Disabled 0 or 33
0 Disabled Disabled Disabled 0
Modulati
ng
hot
water
None 1 100 Enabled. No limit Not applicable Not applicable
0 to 100 (PI
ca
pacity
0.5 to
99
.5
Enabled. Limited
by c
ommunicated
auxiliary heat
enable
Not applicable Not applicable
0 to
C
ommunicated
auxiliary heat
enable value (PI
capacity)
0 Disabled Not applicable Not applicable 0
On/Off
ho
t water
(1 stage)
None 1
0.5 to
10
0
Enabled. On/Off Not applicable Not applicable 0 to 100
0 Disabled Not applicable Not applicable 0
Local heat priority
PWM
elec
tric
(1 to 2
stages)
On/Off
elec
tric
(1 stage)
2
50.5 to
10
0
Enabled. No limit Enabled. On/Off Not applicable 0, 50, or 100
50 Enabled. No limit Disabled Not applicable 0 or 50
0.5 to
49
.5
Enabled. Limited
by c
ommunicated
auxiliary heat
enable
Disabled Not applicable
0 or
Communicated
auxiliary heat
enable value
0 Disabled Disabled Not applicable 0
3
67.5 to
10
0
Enabled. No limit Enabled. No limit Enabled. On/Off 0, 33, 67, or 100
67 Enabled. No limit Enabled. No limit Disabled 0, 33, or 67
34 to
66
.5
Enabled. No limit
Enabled. Limited
by c
ommunicated
auxiliary heat
enable
Disabled
0, 33 or
C
ommunicated
auxiliary heat
enable value
33.5 Enabled. No limit Disabled Disabled
0 or 33
Table 64. Effect of communicated auxiliary heat enable value on heat outputs (continued)
Configuration
Total
number
of heat
stages
Commu
nicated
auxiliar
y heat
enable
value
a
Stage 1 Stage 2 Stage 3
Unit status,
heat_output_
secondary
Local Remote

Table of Contents

Other manuals for Trane Tracer VV550

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Tracer VV550 and is the answer not in the manual?

Trane Tracer VV550 Specifications

General IconGeneral
BrandTrane
ModelTracer VV550
CategoryController
LanguageEnglish

Related product manuals