6 TTA-SVN03A-EN
Electrical Data
Table 1. TTA Unit Electrical Data
Basic Unit Characteristics Compressor Motor Outdoor Fan Motor
Allowable Minimum Maximum
Model Electrical Voltage Circuit Fuse Amps Amps
Number Characteristics Range Ampacity Size Qty. RLA LRA Qty. HP FLA LRA
TTA240F3 208-230/60/3 187-254 89.4 110 2 35.3 239.0 2 1 5.0 14.4
TTA240F4 460/60/3 414-506 46.6 60 2 18.5 125.0 2 1 2.5 5.8
TTA240FK 380/60/3 342-418 - - 2 - - 2 1 3.4 7.8
TTA240FW 575/60/3 578-632 36.0 50 2 14.2 80.0 2 1 2.0 5.1
TTA200FD 380-415/50/3 380-415 48.8 60 2 20.0 118.0 2 1 1.9 5.8