Figure 32. RTAM module
Start Up
RT-SVX25Q-EN 41
Final System Set Up
After completing all of the pre-start and start-up
procedures outlined in the previous sections (i.e.,
operating the unit in each of its modes through all
available stages of cooling and heating), perform these
final checks before leaving the unit:
Program the Night Setback (NSB) panel (if applicable)
fo
r proper
unoccupied operation. Refer to the
programming instructions for the specific panel.
Verify that the Remote panel “System” selection
sw
itch, “Fan
” selection switch, and “Zone
Temperature” settings for automatic operation are
correct.
Inspect the unit for mispl
aced tool
s, hardware, and
debris.
Verify that all exterior panels including the control
panel do
ors and condenser grilles are secured in place.
Close the main disconnect switch
or circui
t protector
switch that provides the supply power to the unit’s
terminal block or the unit mounted disconnect switch.