EasyManua.ls Logo

Trane Voyager TS 150-300 Series - Final Process

Trane Voyager TS 150-300 Series
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Maintenance
54 RT-SVX25Q-EN
instructions as closely as possible to avoid damaging the
coils.
Microchannel (MCHE) Coils
NOTICE
Coil Damage!
Failure to follow instructions below could result in coil
damage.
DO NOT use any detergents with microchannel
condenser coils.
Use pressurized water or air ONLY, with pressure no
greater tha
n 600psi.
For additional information regarding the proper
microchann
el coil cleaning procedure, refer to RT-
SVB83*-EN.
Due to the soft material and thin walls of the MCHE coils,
the traditional field maintenance method recommended
for Round Tube Plate Fin (RTPF) coils does not apply to
microchannel coils.
Moreover, chemical cleaners are
a risk fa
ctor to MCHE due
to the material of the coil. The manufacturer does not
recommend the use of chemical cleaners to clean
microchannel coils. Using chemical cleaners could lead to
warranty claims being further evaluated for validity and
failure analysis.
The recommended cleaning method for microchannel
coi
ls is
pressurized water or air with a non-pinpoint nozzle
and an ECU of at least 180 with pressure no greater than
600 psi. To minimize the risk of coil damage, approach the
cleaning of the coil with the pressure washer aimed
perpendicular to the face of the coil during cleaning.
Optimum clearance between the sprayer nozzle and the
microchannel coil is 1”–3”.
Final Process
For future reference, you may find it helpful to record the
unit data requested below in the blanks provided.
(1) Complete Unit Model Number:
_____________________________________________________
(2) Unit Serial Number:
_____________________________________________________
(3) Wiring Diagram Numbers (from unit control panel)
— schematic(s)
_____________________________________________________
_________
_____________________________
_______________
— connection(s)
_____________________________________________________
______________________________________
______________
_
Table 19. Sample maintenance log
Date
Current
Ambien
t
Temp F/C
Refrigerant Circuit #1 Refrigerant Circuit #2
Compr.
Oil Level
Suct.
Press.
Psig
/kPa
Disch.
Press
Ps
ig/kPa
Liquid
Press
Psig/kPa
Super-
heat F/C
Sub-
cool
F/C
Compr.
Oil Level
Suct.
Pre
ss.
Psig/k
Pa
Disch.
Press
Ps
ig/kPa
Liquid
Press
Psig/kPa
Super-
heat F/C
Sub-cool
F/C
- ok
- low
- ok
- l
ow
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low

Related product manuals