BAS-SVX40A-EN 15
Mounting and Wiring the WCI
Figure 8. Wiring the WCI to a UC400 or a UC600
Figure 9. Wiring the WCI to a BCI-I
Figure 10. Wiring the WCI to a BCI-R
Gray = LINK -
Blue = LINK+
Black = Ground
Red = 24 Vdc
VAC
24
BI
1
BI
2
BI
3
LINK
IMC
+
24
VDC
IM
C
Jumper
LINK -
LINK +
+24 Vdc
WCI
BCI-I
Attach jumper at BI1
to enable wireless
communication.
Gray = LINK -
Blue = LINK +
Black = Ground
Red = 24 Vdc
BCI-R Board
Gray = IMC–
Blue = IMC+
Slide switch to IMC
RTRM
Black = Ground
Red = 24 Vac