RT-SVX23D-EN 49
Maintenance
Record this data on an “operator’s maintenance log” like the one shown in Tabl e 9 . If the operating
pressures indicate a refrigerant shortage, measure the system superheat. For guidelines, refer to
the “Compressor Start-Up” section.
Note: Do Not release refrigerant to the atmosphere! If adding or removing refrigerant is required,
the service technician must comply with all federal, state and local laws.
Heating Season
Inspect the unit’s air filters. If necessary, clean or replace them.
Check supply fan motor bearings; repair or replace the motor as necessary.
Inspect both the main unit control panel and heat section control box for loose electrical
components and terminal connections, as well as damaged wire insulation. Make any
necessary repairs.
Verify that the electric heat system operates properly.
Coil Cleaning
Regular coil maintenance, including annual cleaning, enhances the unit’s operating efficiency by
minimizing: compressor head pressure and amperage draw; evaporator water carryover; fan brake
horsepower, due to increase static pressure losses; airflow reduction.
At least once each year, or more often if the unit is located in a “dirty” environment, clean the
evaporator and condenser coils using the instructions outlined below. Be sure to follow these
instructions as closely as possible to avoid damaging the coils.
Note: For units equipped with hail guards follow removal procedure listed below.
Hail Guard Removal
Unlatch hail guards.
Pull the top of the hail guard outward until the fastener studs are free of the retaining nuts.
Lift the hail guard from the lower retaining bracket and set aside.
To clean refrigerant coils, use a soft brush and a sprayer (either a garden pump-up type or a high-
pressure sprayer). A high-quality detergent is also required; suggested brands include “SPREX
A.C., “OAKITE 161”, “OAKITE 166” and “COILOX”. If the detergent selected is strongly alkaline (ph
value exceeds 8.5), add an inhibitor.
Figure 30. Slide-style and ball-style latches
HAIL GUARD